GE NX-8 Installation Manual - Page 23
LOCATION 49- AUXILIARY OUTPUT #3, EVENT AND TIME 2 segments, numerical data
UPC - 782136401462
View all GE NX-8 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 23 highlights
Location 44 contains the "Duress" code. This Location contains either 4 or 6 digits. If the 6-digit code option is enabled in Location 41, THIS CODE MUST CONTAIN SIX (6) DIGITS. If the 6-digit option is not enabled in location 41, the last 2 digits will be ignored. If the duress code is programmed, it will work for all partitions. LOCATION 45 - AUXILIARY OUTPUT 1-4 PARTITION SELECTION (4 segments, feature selection data) Location 45 is used to select which partition(s) the events must occur in before the output will activate. Location 45 has 4 segments. Segment 1 corresponds to output 1, and Segment 4 corresponds to output 4. Segment 1 (Auxiliary 1) 1= Partition #1 2= Partition #2 3= Partition #3 4= Partition #4 5= Partition #5 6= Partition #6 7= Partition #7 8= Partition #8 Segment 2 (Auxiliary 2) 1= Partition #1 2= Partition #2 3= Partition #3 4= Partition #4 5= Partition #5 6= Partition #6 7= Partition #7 8= Partition #8 Segment 3 (Auxiliary 3) 1= Partition #1 2= Partition #2 3= Partition #3 4= Partition #4 5= Partition #5 6= Partition #6 7= Partition #7 8= Partition #8 Segment 4 (Auxiliary 4) 1= Partition #1 2= Partition #2 3= Partition #3 4= Partition #4 5= Partition #5 6= Partition #6 7= Partition #7 8= Partition #8 LOCATION 46 - AUXILIARY OUTPUT 1-4 SPECIAL TIMING (4 segments, feature selection data) Location 46 contains special timing feature activation for the four auxiliary outputs. Segment 1 corresponds to output 1, Segment 4 corresponds to output 4. Segments 1 - 4: 1 = On if output should be timed in minutes; Off if timed in seconds. 2 = On if output should latch; Off if output should be timed. 3 = On if output should stop timing upon code entry; Off if the output should continue to time upon code entry. 4 = On if output should only activate between the closing and opening time in loc. 52 and 53. 5 = On if output should only activate between the opening and closing time in loc. 52 and 53. 6 = On if output should be inverted (0 volts going to 12 volts when activated). 7 = Reserved. 8 = Reserved. LOCATION 47 - AUXILIARY OUTPUT #1, EVENT AND TIME (2 segments, numerical data) Segment 1: Segment 2: Use the chart on page 24 to select the event that will activate Auxiliary Output 1. Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 1, Location 46). Programming a "0" makes the output follow the event. LOCATION 48 - AUXILIARY OUTPUT #2, EVENT AND TIME (2 segments, numerical data) Segment 1: Segment 2: Use the chart on page 24 to select the event that will activate Auxiliary Output 2. Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 2, Location 46). Programming a "0" makes the output follow the event. LOCATION 49- AUXILIARY OUTPUT #3, EVENT AND TIME (2 segments, numerical data) Segment 1: Segment 2: Use the chart on page 24 to select the event that will activate Auxiliary Output 3. Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 3, Location 46). Programming a "0" makes the output follow the event. LOCATION 50- AUXILIARY OUTPUT #4, EVENT AND TIME (2 segments, numerical data) Segment 1: Segment 2: Use the chart on page 24 to select the event that will activate Auxiliary Output 4. . Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 4, Location 46). Programming a "0" makes the output follow the event. Page 23