units power supply indoor fan motor power input(W) model phase FQY voltage volt. range MCA MFA W FLA cooling heating AC162MCERA 1 50 220 198~242 0.45 1.44 26 0.36 60 60 AC182MCERA 1 50 220 198~242 0.45 1.44 26 0.36 60 60 AC242MCERA 1 50 220 198~242 0.45 1.44 26 0.36 100 100 AC382MFERA 1 50 220 198~242 1.69 5.4 100 1.35 100 100 AC482MFERA 1 50 220 198~242 1.69 5.4 100 1.35 100 100 AS072MCERA 1 50 220 198~242 0.3 0.96 15 0.24 27 27 AS092MCERA 1 50 220 198~242 0.3 0.96 15 0.24 27 27 AS122MCERA 1 50 220 198~242 0.3 0.96 15 0.24 27 27 AS162MCERA 1 50 220 198~242 0.35 1.12 26 0.28 45 45 AS182MCERA 1 50 220 198~242 0.35 1.12 26 0.28 45 45 AF072MCERA 1 50 220 198~242 0.28 0.88 20 0.22 27 27 AF092MCERA 1 50 220 198~242 0.28 0.88 20 0.22 27 27 AF122MCERA 1 50 220 198~242 0.28 0.88 20 0.22 27 27 AF182MCERA 1 50 220 198~242 0.32 1.00 30 0.25 45 45 Symbols: MCA: Min. circuit amps (A) MFA: Max. fuse amps of circuit breaker KW: Fan motor rated output (KW) FLA: Full load amps(A) IFM: Indoor fan motor Notes: 1. Voltage range The units are applicable for the electrical systems where voltage supplied to unit is in the range. 2. Maximum allowable voltage unbalance between phases is 2%. 3. MCA=1.25*FLA MFA 4*FLA 4. Power supply uses the circuit breaker G R U P A d.o.o. 107