4. Pipe specifications and connection methods (unit: mm) A. Outdoor unit Model AV08NMVERA AV10NMVERA Gas pipe side Diameter Connecting method 19.05 22.22 Brazing Liquid pipe side Diameter Connecting method 9.52 Flared joint Oil pipe side Diameter Connecting method Flared 9.52 joint AV12NMVERA AV14NMVERA AV16NMVERA 25.4 25.4 28.58 Brazing 12.7 Flared joint 9.52 Flared joint B. Indoor unit Model Capacity 07 09 12 14 16 18 24 28 32 38 48 Diameter 9.52 Gas pipe side Connecting method 9.52 12.7 12.7 12.7 Flared joint 12.7 15.88 15.88 15.88 15.88 15.88 C. Pipe spec and the torque diameter Thickness(mm) 6.35 0.8 9.52 0.8 12.7 1.0 15.88 1.0 19.05 1.0 25.4 1.2 Not less than 28.58 More than 1.4 Torque(N.m) 16~20 40~50 90~120 100~140 ----- Diameter 6.35 6.35 6.35 6.35 6.35 Liquid pipe side Connecting method Flared joint 6.35 9.52 9.52 9.52 9.52 9.52 5. Refrigerant charging and additional charging Diameter of liquid pipe Model AV08NMVERA AV10NMVERA AV12NMVERA AV14NMVERA AV16NMVERA additonal refrigerant charging per meter(kg/m) 22.22 19.05 15.88 12.7 9.52 6.35 0.35 0.25 0.17 0.11 0.054 0.022 charge when out of factory 10kg 12kg 16kg G R U P A d.o.o. 92