Haier AV16NMVERA Design Manual - Page 86
Av46nmvera, Av44nmvera, Av40nmvera, Av38nmvera, Av34nmvera, Av48nmvera, Av42nmvera, Av36nmvera,
View all Haier AV16NMVERA manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 86 highlights
cooling compensation factor AV32NMVERA 1.00 0.95 0.90 0.85 liquid pipe:φ19.05 gas pipe:φ31.8 0.80 liquid pipe:φ19.05 gas pipe:φ38.1 0 20 40 60 80 100 120 140 160 180 pipe length of single way (m) AV36NMVERA 1.00 0.95 cooling compensation factor AV34NMVERA 1.00 0.95 liquid pipe:φ19.05 gas pipe:φ38.1 0.90 0.85 liquid pipe:φ19.05 gas pipe:φ31.8 0.80 0 20 40 60 80 100 120 140 160 180 pipe length of single way (m) 1.00 0.95 AV38NMVERA liquid pipe:φ22.22 gas pipe:φ38.1 cooling compensation factor cooling compensation factor cooling compensation factor 0.90 0.85 liquid pipe:φ19.05 gas pipe:φ38.1 0.80 liquid pipe:φ22.22 gas pipe:φ38.1 0 20 40 60 80 100 120 140 160 180 pipe length of single way (m) 0.90 0.85 liquid pipe:φ19.05 gas pipe:φ38.1 0.80 0 20 40 60 80 100 120 140 160 180 pipe length of single way (m) cooling compensation factor 1.00 0.95 AV40NMVERA liquid pipe:φ22.22 gas pipe:φ38.1 1.00 0.95 AV42NMVERA 0.90 0.85 liquid pipe:φ19.05 gas pipe:φ38.1 0.80 0 20 40 60 80 100 120 140 160 180 pipe length of single way (m) 1.00 0.95 AV44NMVERA liquid pipe:φ22.22 gas pipe:φ38.1 0.90 0.85 liquid pipe:φ19.05 gas pipe:φ38.1 0.80 liquid pipe:φ22.22 gas pipe:φ38.1 0 20 40 60 80 100 120 140 160 180 pipe length of single way (m) AV46NMVERA 1.00 0.95 liquid pipe:φ22.22 gas pipe:φ38.1 cooling compensation factor 0.90 0.85 liquid pipe:φ19.05 gas pipe:φ38.1 0.80 0 20 40 60 80 100 120 140 160 180 pipe length of single way (m) AV48NMVERA 0.90 0.85 liquid pipe:φ19.05 gas pipe:φ38.1 0.80 0 20 40 60 80 100 120 140 160 180 pipe length of single way (m) 1.00 cooling compensation factor cooling compensation factor 0.95 0.90 0.85 0.80 liquid pipe:φ19.05 gas pipe:φ38.1 liquid pipe:φ22.22 gas pipe:φ38.1 0 20 40 60 80 100 120 140 160 180 Note: pipe length of single way (m) 1. The refrigerant pipe should be thickened when the single way length is over 90m. 2. When in cooling mode, outdoor is lower than indoor; or when in heating mode, outdoor is higher than indoor, the compensation factor should be decreased the below value from the above figure. vertical height drop between indoor and outdoor adjustment factor 5m 10m 15m 20m 25m 30m 35m 40m 45m 50m 0.003 0.006 0.009 0.012 0.015 0.018 0.021 0.024 0.027 0.030 G R U P A d.o.o. 86