Haier AV16NMVERA Design Manual - Page 87
x A x B x C x D x E x F W
View all Haier AV16NMVERA manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 87 highlights
(2) Calculation method of heating capacity---Heating capacity to be known = Heating capacityx (A x B x C x D x E x F) W A. Capacity modification value under indoor air dry-bulb temperature condition 1.2 1.1 1.0 0.9 0.8 15 20 24 Indoor air dry-bulb temperature B. Capacity modification value under outdoor air wet-bulb temperature condition 1.2 1.1 1.0 0.9 0.8 0.7 0.6 0.5 -15 -10 -5 0 5 10 15 Outdoor air wet-bulb temperature Capacity modification value C. Capacity modification value under airflow variation rate of indoor unit group 1.1 1.0 0.9 80 90 100 110 120 airflow variation rate(%) D. Capacity compensation suitable for total capability of indoor unit group (heating) 1.2 1.0 E. Capacity compensation coefficient for defrost capability of outdoor heat exchanger 1.0 Capacity modification coefficient Capacity modification coefficient 0.8 0.6 0.9 0.4 Standard capacity 0.2 0.8 0 20 40 60 80 100 120 140 -15 -10 -5 0 5 Outdoor air wet-bulb temperature 10 Total capacity of indoor unit group(%) F. Heating compensation factor at different pipe length heating compensation factor 1.00 for all models 0.98 0.96 0.94 0.92 0.90 0 20 40 60 80 100 120 140 160 180 pipe length of single way (m) (3) Calculation method of refrigerating capacity---Only one indoor unit running Outdoor modified capacity with a single indoor running = outdoor modified capacity * standby indoor nominal capacity Indoor total nominal capacity (Outdoor modified capacity: heating or cooling capacity after modify item 1 and 2) G R U P A d.o.o. 87