Honeywell HPF24S6 Installation Manual - Page 12

HPF24S Board Layout, Special Application or Regulated

Page 12 highlights

System Overview Specifications Power-limited (Class 2), Supervised, Special Application or Regulated Nonpower-limited To Transformer #1 To Transformer #2 Supervised, Nonpower-limited Earth AC Neutral AC Hot NAC/Out 1 + NAC/Out 1 NAC/Out 2 + NAC/Out 2 NAC/Out 3 + NAC/Out 3 NAC/Out 4 + NAC/Out 4 - EARTH NEUT HOT TB1 OUT4 - NAC4 + 8 7 OUT3 - NAC3 + 6 5 OUT2 - NAC2 + 4 3 OUT1 - NAC1 + 2 1 TB2 AUX TBL NO NC COM TB5 3 2 1 Trouble Relay Form-C Fail-safe Nonsupervised (shown energized) Normally Open Normally Closed Common TRANSFORMER 2 TRANSFORMER 1 JP1 Ground Fault Detection J2 (cut to disable) JP1 J3 J3 JP2 ZNAC-4 Connector JP2 & JP3 JP3 Coded/Noncoded J1 Input Selection Auxiliary Output 500 mA Special AUX - 10 Application Power* AUX + 9 IN2- 8 IN2+ 7 OUT1- 6 OUT1+ 5 IN1- 4 F1 IN1+ 3 - + JP4 BATTERY AC GND FLT NAC AC/ BATT TRBL CHGR ON SW1 1 2 3 4 5 6 7 8 SYNC IN - 2 SYNC IN + 1 TB4 JP4 Supervised + Battery - Battery 18 AH, 24 VDC Nonpower- F1 limited Battery Fuse 15A, 32V (Canadian version is nonreplaceable 12 A, 32V) SW1 LEDs Programming Charger Trouble/AC Loss (yellow) DIP Switches NAC Trouble (yellow) (change switch settings only Battery Trouble (yellow) when all power Ground Fault (yellow) (AC & DC) is AC Power (green) removed) Figure 1.1 HPF24S Board Layout - Aux. Common + Aux. 24 VDC* - Control Input 2 + Control Input 2 - Out Common + Out/Trouble Contact - Control Input 1 + Control Input 1 - Sync Input + Sync Input *Note: Auxiliary Power Output is power-limited (Class 2) but not supervised 24fs8brd.wmf 12 HPF24S Series Power Supplies - P/N 52751:F2 7/11/2014

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

12
HPF24S Series Power Supplies —
P/N 52751:F2
7/11/2014
System Overview
Specifications
1
2
3
4
5
6
7
8
ON
TB1
J2
TRANSFORMER 2
TRANSFORMER 1
J1
F1
JP4
SW1
TB4
JP3
J3
TB5
TB2
JP1
JP2
-
+
EARTH NEUT
HOT
OUT4
- NAC4 +
OUT3
- NAC3 +
OUT2
- NAC2 +
OUT1
- NAC1 +
8
7
6
5
4
3
2
1
3
2
1
10
9
8
7
6
5
4
3
2
1
AUX -
IN2-
IN2+
OUT1-
OUT1+
IN1-
IN1+
SYNC IN -
SYNC IN +
AUX +
NO
NC
AUX TBL
COM
BATTERY
AC
BATT
AC/
CHGR
GND
FLT
NAC
TRBL
Figure 1.1
HPF24S Board Layout
- Aux. Common
+ Aux. 24 VDC*
- Control Input 2
+ Control Input 2
- Out Common
+ Out/Trouble Contact
- Control Input 1
+ Control Input 1
- Sync Input
+ Sync Input
NAC/Out 1 +
NAC/Out 1 -
NAC/Out 2 +
NAC/Out 2 -
NAC/Out 3 +
NAC/Out 3 -
NAC/Out 4 +
NAC/Out 4 -
Supervised,
Nonpower-limited
Earth
AC Neutral
AC Hot
Trouble Relay
Form-C Fail-safe
Nonsupervised
(shown energized)
Normally Open
Normally Closed
Common
JP1
Ground Fault
Detection
(cut to disable)
JP2 & JP3
Coded/Noncoded
Input Selection
JP4
Supervised
+ Battery
- Battery
18 AH, 24 VDC
Nonpower-
limited
LEDs
Charger Trouble/AC Loss (yellow)
NAC Trouble (yellow)
Battery Trouble (yellow)
Ground Fault (yellow)
AC Power (green)
SW1
Programming
DIP Switches
(change switch
settings only
when all power
(AC & DC) is
removed)
F1
Battery Fuse
15A, 32V
(Canadian version
is
nonreplaceable
12 A, 32V)
Nonpower-limited
To Transformer #1
To Transformer #2
Auxiliary Output
500 mA Special
Application Power*
J3
ZNAC-4 Connector
*Note: Auxiliary Power
Output is power-limited
(Class 2) but not
supervised
Power-limited (Class 2), Supervised,
Special Application or Regulated
24fs8brd.wmf