Honeywell HPF24S6 Installation Manual - Page 36

Master HPF24S Power Supply Connected to FACP, 5.7 Canadian Applications,

Page 36 highlights

Applications Master HPF24S Power Supply Connected to FACP 5.6 Master HPF24S Power Supply Connected to FACP In this application, a master HPF24S power supply, set for synchronization, is connected to an FACP with nonsynchronized output. Standby Polarity Shown FACP NAC with no syncronization - NAC1 + Internal Trouble Contact HPF24S 1 2 3 4 5 6 7 8 9 10 ELR for FACP NAC OUT4 OUT3 OUT2 OUT1 -NAC4+ -NAC3+ -NAC2+ -NAC1+ TB2 AUX TBL NO NC COM TB5 JP1 J3 JP2 JP3 AUX AUX + IN2IN2+ OUT1OUT1+ IN1IN1+ SYNC IN SYNC IN + TB4 8 7 6 5 4 3 2 1 3 2 1 24fsapp11b.wmf SW1 Switch Settings 1 & 2 = sync (any setting but OFF/OFF) 3 = OFF (master) 4 = OFF (No AC Fail Reporting Delay) 5 = 6 = OFF OFF general alarm 7 = OFF (charger enabled) 8 = OFF (circuit 4 NAC) Figure 5.6 Supervised FACP to Master Connections (nonsynchronized source) The following notes apply to this illustration 1. Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode. 2. Use only devices from the same manufacturer in each system. 5.7 Canadian Applications NOTE: Mass Notification is not for use in Canadian applications. Canadian applications, per ULC, require the following: • The HPF24S power supply must be used as a Notification Appliance Circuit extender only. The TB2 terminals cannot be configured as auxiliary power outputs. • The host FACP must monitor for all ground fault conditions. The Ground Fault Detection circuit on the HPF24S power supply must be disabled by cutting jumper JP1. • The negative (-) battery terminal of the HPF24S power supply must be connected to the negative (-) battery terminal of the host FACP. 36 HPF24S Series Power Supplies - P/N 52751:F2 7/11/2014

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

36
HPF24S Series Power Supplies —
P/N 52751:F2
7/11/2014
Applications
Master HPF24S Power Supply Connected to FACP
5.6
Master HPF24S Power Supply Connected to FACP
In this application, a master HPF24S power supply, set for synchronization, is connected to an
FACP with nonsynchronized output.
The following notes apply to this illustration
1.
Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2.
Use only devices from the same manufacturer in each system.
5.7
Canadian Applications
Canadian applications, per ULC, require the following:
The HPF24S power supply must be used as a Notification Appliance Circuit extender only.
The TB2 terminals cannot be configured as auxiliary power outputs.
The host FACP must monitor for all ground fault conditions.
The Ground Fault Detection
circuit on the HPF24S power supply must be disabled by cutting jumper JP1.
The negative (-) battery terminal of the HPF24S power supply must be connected to the
negative (-) battery terminal of the host FACP.
-
+
TB4
JP3
J3
TB5
TB2
JP1
JP2
OUT4
-NAC4+
OUT3
-NAC3+
OUT2
-NAC2+
OUT1
-NAC1+
AUX -
IN2-
IN2+
OUT1-
OUT1+
IN1-
IN1+
SYNC IN -
SYNC IN +
AUX +
NO NC
AUX TBL
COM
1
2
3
4
5
6
7
8
9
10
8
7
6
5
4
3
2
1
3
2
1
Standby Polarity Shown
HPF24S
SW1 Switch Settings
1 & 2 = sync (any setting
but OFF/OFF)
3 = OFF (master)
4 = OFF (No AC Fail
Reporting Delay)
5 = OFF
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Figure 5.6
Supervised FACP to Master Connections (nonsynchronized source)
general alarm
24fsapp11b.wmf
FACP
NAC with no
syncronization
NAC1
Internal Trouble
Contact
ELR for
FACP
NAC
NOTE:
Mass Notification is not for use in Canadian applications.