Master FACP with Slave HPF24S Power Supply, Supervised Master/Slave Connections

Page 35 highlights

Master FACP with Slave HPF24S Power Supply Applications 5.5 Master FACP with Slave HPF24S Power Supply In this application, an HPF24S power supply, configured as a Slave unit, is connected to a master FACP programmed for synchronized output. The power supply should be set for synchronization which matches the FACP programming. Standby Polarity Shown FACP See Note 3 - NAC1 (programmed for sync) + Internal Trouble Contact HPF24S 1 2 3 4 5 6 7 8 9 10 ELR OUT4 OUT3 OUT2 OUT1 -NAC4+ -NAC3+ -NAC2+ -NAC1+ TB2 AUX TBL NO NC COM TB5 JP1 J3 JP2 JP3 AUX AUX + IN2IN2+ OUT1OUT1+ IN1IN1+ SYNC IN SYNC IN + TB4 SW1 Switch Settings 1 & 2 = sync (any setting 8 but OFF/OFF) 7 6 3 = ON (slave) 5 4 4 = OFF (no AC Fail 3 2 reporting delay) 1 3 5 6 = = OFF OFF general alarm 2 1 7 = OFF (charger enabled) 8 = OFF (circuit 4 NAC) 24fsapp1c.wmf Figure 5.5a: Supervised Master/Slave Connections (Filtered, Synchronized NAC Source) Standby Polarity Shown FACP - Remote Sync Output + OUT4 OUT3 OUT2 OUT1 -NAC4+ -NAC3+ -NAC2+ -NAC1+ TB2 AUX TBL NO NC COM TB5 JP1 J3 JP2 JP3 AUX AUX + IN2IN2+ OUT1OUT1+ IN1IN1+ SYNC IN SYNC IN + TB4 Internal Trouble Contact 1 2 3 4 5 6 7 8 9 10 ELR SW1 Switch Settings 1 & 2 = sync (any setting 8 7 but OFF/OFF) 6 5 3 = ON (slave) 4 3 4 = OFF (no AC Fail 2 reporting delay) 1 5 = OFF 3 2 6 = OFF 1 7 = OFF (charger enabled) 8 = OFF (circuit 4 NAC) 24fsapp1b.wmf Figure 5.5b: Supervised Master/Slave Connections (Remote Sync Source) Figure 5.5 Supervised Master/Slave Connections The following notes apply to both illustrations in Figure 5.5 on page 35 1. Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode. 2. Use only devices from the same manufacturer in each system. 3. If the FACP has a dedicated sync output connector, wire the remote sync output connector to the HPF24S Sync In terminals TB4 terminals 1 & 2. Refer to the Supervised Master/Slave Connections (Remote Sync Source) in Figure 5.5b. HPF24S Series Power Supplies - P/N 52751:F2 7/11/2014 35

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

HPF24S Series Power Supplies —
P/N 52751:F2
7/11/2014
35
Master FACP with Slave HPF24S Power Supply
Applications
5.5
Master FACP with Slave HPF24S Power Supply
In this application, an HPF24S power supply, configured as a Slave unit, is connected to a master
FACP programmed for synchronized output.
The power supply should be set for synchronization
which matches the FACP programming.
The following notes apply to both illustrations in Figure 5.5 on page 35
1.
Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2.
Use only devices from the same manufacturer in each system.
3.
If the FACP has a dedicated sync output connector, wire the remote sync output connector to
the HPF24S Sync In terminals TB4 terminals 1 & 2.
Refer to the Supervised Master/Slave
Connections (Remote Sync Source) in Figure 5.5b.
-
+
TB4
JP3
J3
TB5
TB2
JP1
JP2
OUT4
-NAC4+
OUT3
-NAC3+
OUT2
-NAC2+
OUT1
-NAC1+
AUX -
IN2-
IN2+
OUT1-
OUT1+
IN1-
IN1+
SYNC IN -
SYNC IN +
AUX +
NO NC
AUX TBL
COM
1
2
3
4
5
6
7
8
9
10
8
7
6
5
4
3
2
1
3
2
1
ELR
-
+
TB4
JP3
J3
TB5
TB2
JP1
JP2
OUT4
-NAC4+
OUT3
-NAC3+
OUT2
-NAC2+
OUT1
-NAC1+
AUX -
IN2-
IN2+
OUT1-
OUT1+
IN1-
IN1+
SYNC IN -
SYNC IN +
AUX +
NO NC
AUX TBL
COM
1
2
3
4
5
6
7
8
9
10
8
7
6
5
4
3
2
1
3
2
1
ELR
Standby Polarity Shown
HPF24S
SW1 Switch Settings
1 & 2 = sync (any setting
but OFF/OFF)
3 = ON (slave)
4 = OFF (no AC Fail
reporting delay)
5 = OFF
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Figure 5.5
Supervised Master/Slave Connections
general alarm
24fsapp1c.wmf
See Note 3
24fsapp1b.wmf
SW1 Switch Settings
1 & 2 = sync (any setting
but OFF/OFF)
3 = ON (slave)
4 = OFF (no AC Fail
reporting delay)
5 = OFF
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Figure 5.5a: Supervised Master/Slave Connections (Filtered, Synchronized NAC Source)
Figure 5.5b: Supervised Master/Slave Connections (Remote Sync Source)
Standby Polarity Shown
FACP
NAC1
(programmed
for sync)
Internal Trouble
Contact
FACP
Remote Sync
Output
Internal Trouble
Contact