Honeywell HPF24S6 Installation Manual - Page 34

Remote Power Supply Application, HPP Device Compatibility Document #54399

Page 34 highlights

Applications Remote Supply With Resettable and Nonresettable Power For addressable panel applications, an addressable monitor module can be used to monitor the trouble contact of the HPF24S and the resettable power connection from the FACP using an End-ofLine power supervision relay. If the HPF24S enters a trouble condition, the Normally Closed trouble contact will open and if the resettable power from the FACP is lost, the Normally Closed power supervision relay contact will open. HPF24S 24 VDC Resettable Power FACP Power Output 4 Nonresettable Power Output 3 Nonresettable Power Output 2 Resettable Power Output 1 Resettable T11 T10 T9 T8 T7 T6 SLC T1 T2 T3 T4 T5 End-of-Line Resistor supplied with Monitor Module SW1 Switch Settings 1 = OFF 2 = OFF No Sync 3 = OFF (master) 4 = ON (Aux Trouble Relay responds to all troubles) 5 6 = = OFF ON Split Alarm 7 = OFF (charger enabled) 8 = OFF (circuit 4 NAC) EOL Power Supervision Relay EOLR-1 (energized) Monitor Module* *If the SLC device does not match the one in this figure, refer to the SLC SLC manual wiring conversion charts for legacy and newer versions of the modules. 24fsapp4tpH.wmf Figure 5.4 Remote Power Supply Application The following notes apply to Figure 5.4 on page 34. 1. An End-of-Line Resistor must be installed between TB5, Terminal 1 (trouble relay common) and the monitor module input circuit for module wiring supervision (the ELR value is dependent on the module employed). 2. An End-of-Line power supervision relay must be connected between TB4, Terminals 5 & 6. The Normally Closed (when energized) power supervision relay contact must be in series with the End-of-Line Resistor referred to in note 1. 3. Do not loop wires under screw terminals. Break wires to maintain proper supervision. 4. For a list of compatible devices, refer to the HPP Device Compatibility Document #54399. 34 HPF24S Series Power Supplies - P/N 52751:F2 7/11/2014

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

34
HPF24S Series Power Supplies —
P/N 52751:F2
7/11/2014
Applications
Remote Supply With Resettable and Nonresettable Power
For addressable panel applications, an addressable monitor module can be used to monitor the trou-
ble contact of the HPF24S and the resettable power connection from the FACP using an End-of-
Line power supervision relay.
If the HPF24S enters a trouble condition, the Normally Closed trou-
ble contact will open and if the resettable power from the FACP is lost, the Normally Closed power
supervision relay contact will open.
The following notes apply to Figure 5.4 on page 34.
1.
An End-of-Line Resistor must be installed between TB5, Terminal 1 (trouble relay common)
and the monitor module input circuit for module wiring supervision (the ELR value is
dependent on the module employed).
2.
An End-of-Line power supervision relay must be connected between TB4, Terminals 5 & 6.
The Normally Closed (when energized) power supervision relay contact must be in series with
the End-of-Line Resistor referred to in note 1.
3.
Do not loop wires under screw terminals.
Break wires to maintain proper supervision.
4.
For a list of compatible devices, refer to the
HPP Device Compatibility Document #54399
.
Figure 5.4
Remote Power Supply Application
Power Output 1
Resettable
Power Output 2
Resettable
Power Output 3
Nonresettable
Power Output 4
Nonresettable
SLC
SLC
Monitor Module*
FACP
24 VDC
Resettable
Power
HPF24S
EOL Power
Supervision
Relay
EOLR-1
(energized)
SW1 Switch Settings
1 = OFF
2 = OFF
3 = OFF (master)
4 = ON (Aux Trouble Relay responds
to all troubles)
5 = OFF
6 = ON
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Split Alarm
No Sync
End-of-Line Resistor supplied
with Monitor Module
24fsapp4tpH.wmf
*If the SLC device does
not match the one in this
figure, refer to the SLC
manual wiring conversion
charts for legacy and newer
versions of the modules.
T11
T10
T9
T8
T7
T6
T1
T2
T3
T4
T5