Honeywell HPF24S6 Installation Manual - Page 40
Table 6.3, System Current Draw Calculations, When finished, copy the totals from Calcu
View all Honeywell HPF24S6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 40 highlights
Power Supply Requirements Calculating the System Current Draw Table 6.3 contains three columns for calculating current draws. For each column, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 6.4 on page 41. Device Type Calculate Column 1 Primary, Non-Fire Alarm Current (amps) Calculate Column 2 Primary, Fire Alarm Current (amps) Qty X (current draw) = Total Main Circuit Board 1 X [ 0.091] = Power [ ] Supervision Relay X [ 0.025] = NAC/Output #1 NAC/Output #2 NAC/Output #3 NAC/Output #4 Current Draw from TB4 Terminals 9 & 10 [ ]= Qty X (current draw) = Total 1 X [ 0.145] = [ ] X [0.025 ] = X[ ]= X[ ]= X[ ]= X[ ]= [ ]= Calculation Column 3 Secondary, Non-Fire Alarm Current (amps) Qty X (current draw) = Total 1 X [ 0.065] = [ ] X [ 0.025] = [ ]= Sum each column for totals Primary Non-Alarm = Primary Alarm = Secondary Alarm = Table 6.3 System Current Draw Calculations 40 HPF24S Series Power Supplies - P/N 52751:F2 7/11/2014