Honeywell HPF24S6 Installation Manual - Page 17

Addressable Module Mounting, Mounting Module In HPF-24S Cabinet

Page 17 highlights

Addressable Module Mounting Installation 2.3 Addressable Module Mounting The HPF24S has been designed to allow the mounting of an addressable control, relay or monitor module on the main circuit board inside the power supply cabinet with the module status LED visible through the closed door. This allows power to be fed from the HPF24S Auxiliary Power output directly to the module, if needed, without running the power wires outside the cabinet. As an example, Figure 2.5 illustrates wiring from the Auxiliary power output terminals to a CMF-300 control module's terminals 3 (-) and 4 (+). NOTE: The optional module mounting kit (P/N 90286) is required to install an addressable module on the power supply main circuit board. The kit includes four female/female and four male/female standoffs as well as four mounting screws. *If the SLC device does not match the one in this figure, refer to the SLC manual wiring conversion charts for legacy and newer versions of the modules. standoff standoff standoff standoff 24fsmodltpH.wmf Module Installation 1. Remove HPF24S main circuit board from mounting plate by removing four corner screws. 2. Install four male/female standoffs through bottom of board in holes indicated in illustration above. 3. Screw four female/female standoffs to male ends of standoffs installed in Step 2 to secure in place. 4. Place addressable module over standoffs installed in Step 3 and secure with supplied screws. 5. Reinstall main circuit board on mounting plate and wire module as show in illustration above. female/female standoffs female/female standoffs mounting screw addressable module Figure 2.5 Mounting Module In HPF-24S Cabinet 24fsmodinstl.wmf HPF24S Series Power Supplies - P/N 52751:F2 7/11/2014 17

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

HPF24S Series Power Supplies —
P/N 52751:F2
7/11/2014
17
Addressable Module Mounting
Installation
2.3
Addressable Module Mounting
The HPF24S has been designed to allow the mounting of an addressable control, relay or monitor
module on the main circuit board inside the power supply cabinet with the module status LED visi-
ble through the closed door.
This allows power to be fed from the HPF24S Auxiliary Power output
directly to the module, if needed, without running the power wires outside the cabinet. As an exam-
ple, Figure 2.5 illustrates wiring from the Auxiliary power output terminals to a CMF-300 control
module’s terminals 3 (-) and 4 (+).
NOTE:
The optional module mounting kit (P/N 90286) is required to install an addressable
module on the power supply main circuit board.
The kit includes four female/female and four
male/female standoffs as well as four mounting screws.
standoff
standoff
standoff
standoff
24fsmodltpH.wmf
*If the SLC device does not match the one in this figure,
refer to the SLC manual wiring conversion charts for leg-
acy and newer versions of the modules.
Module Installation
1.
Remove HPF24S main circuit board from mounting
plate by removing four corner screws.
2.
Install four male/female standoffs through bottom of
board in holes indicated in illustration above.
3.
Screw four female/female standoffs to male ends of
standoffs installed in Step 2 to secure in place.
4.
Place addressable module over standoffs installed in
Step 3 and secure with supplied screws.
5.
Reinstall main circuit board on mounting plate and
wire module as show in illustration above.
Figure 2.5
Mounting Module In HPF-24S Cabinet
female/female standoffs
female/female standoffs
addressable module
mounting screw
24fsmodinstl.wmf