Appendix A: Wire Requirements Connecting external system accessories to the main circuits must be carefully considered to ensure proper operation. It is important to use the correct type of wire, gauge and run length for each circuit. The following table lists NAC wiring requirements for the HPF24S6 and HPF24S8 Field Charger Power Supply. NAC Load (Amps) Max. allowable total loop resistance (ohms) CLASS-B Max. allowable wire pair lenth (feet) AWG 12 AWG 14 AWG 16 AWG 18 solid solid solid solid CLASS-A Max. allowable wire pair length (feet) AWG 12 AWG 14 AWG 16 AWG 18 solid solid solid solid 0.25 6.00 1554 977 613 386 777 489 307 193 0.5 3.00 777 489 307 193 389 244 153 97 0.75 2.00 518 326 204 129 259 163 102 64 1.0 1.50 389 244 153 97 194 122 77 48 1.25 1.20 311 195 123 77 155 98 61 39 1.5 1.00 259 163 102 64 130 81 51 32 1.75 0.86 222 140 88 55 111 70 44 28 2.0 0.75 194 122 77 48 97 61 38 24 2.25 0.67 173 109 68 43 86 54 34 21 2.5 0.60 155 98 61 39 78 49 31 19 2.75 0.55 141 89 56 35 71 44 28 18 3.0 0.50 130 81 51 32 65 41 26 16 Table A.1 NAC Wiring Requirements for Power Supply NOTE: Calculations are based on Direct-Current Resistance data for uncoated copper wire, per National Electrical Code (2005 Edition) Table 8, Conductor Properties. NOTE: These distances reflect the worst case scenario and are based on the correct draw of the highest candela strobes at the low end of the supported NAC voltage with the entire load at the end of the circuit. Further distances can be achieved by performing a point to point voltage calculation that more accurately reflects the specific devices used and how they are dispersed on the circuit. HPF24S Series Power Supplies - P/N 52751:F2 7/11/2014 43

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

HPF24S Series Power Supplies —
P/N 52751:F2
7/11/2014
43
Appendix A: Wire Requirements
Connecting external system accessories to the main circuits must be carefully considered to ensure
proper operation. It is important to use the correct type of wire, gauge and run length for each cir-
cuit. The following table lists NAC wiring requirements for the HPF24S6 and HPF24S8 Field
Charger Power Supply.
NAC Load
(Amps)
Max.
allowable
total loop
resistance
(ohms)
CLASS-B
Max. allowable wire pair lenth
(feet)
CLASS-A
Max. allowable wire pair length
(feet)
AWG 12
solid
AWG 14
solid
AWG 16
solid
AWG 18
solid
AWG 12
solid
AWG 14
solid
AWG 16
solid
AWG 18
solid
0.25
6.00
1554
977
613
386
777
489
307
193
0.5
3.00
777
489
307
193
389
244
153
97
0.75
2.00
518
326
204
129
259
163
102
64
1.0
1.50
389
244
153
97
194
122
77
48
1.25
1.20
311
195
123
77
155
98
61
39
1.5
1.00
259
163
102
64
130
81
51
32
1.75
0.86
222
140
88
55
111
70
44
28
2.0
0.75
194
122
77
48
97
61
38
24
2.25
0.67
173
109
68
43
86
54
34
21
2.5
0.60
155
98
61
39
78
49
31
19
2.75
0.55
141
89
56
35
71
44
28
18
3.0
0.50
130
81
51
32
65
41
26
16
Table A.1
NAC Wiring Requirements for Power Supply
NOTE:
Calculations are based on Direct-Current Resistance data for uncoated copper wire, per
National Electrical Code (2005 Edition) Table 8, Conductor Properties.
NOTE:
These distances reflect the worst case scenario and are based on the correct draw of the
highest candela strobes at the low end of the supported NAC voltage with the entire load at the
end of the circuit. Further distances can be achieved by performing a point to point voltage
calculation that more accurately reflects the specific devices used and how they are dispersed on
the circuit.