Honeywell HPF24S6 Installation Manual - Page 32

Split Temporal Mode of Operation, Split Temporal Mode Application

Page 32 highlights

Applications Split Temporal Mode of Operation 5.3 Split Temporal Mode of Operation In this application, the power supply has been set as a master with two synchronized and two nonsynchronized outputs as determined by the Split Temporal mode feature. Control Input #1 (TB4, Terminals 3 & 4) is connected to an addressable control module which will cause the synchronized power supply output circuits 1 & 2 to turn on. Control Input #2 (TB4, Terminals 7 & 8) is connected to an FACP Notification Appliance Circuit which is used to activate the power supply's temporal output circuits 3 & 4. Note: All NACs are supervised and power-limited (Class 2) OUT4 -NAC4+ OUT4 -NAC4+ ELR not required Style Z (Class A) for NAC - + -+ Bells TB2 -8 +7 -+ - + Use listed ELR (4.7K) to -+ terminate Style Y (Class B) NAC -+ Bells TB2 8 7 -+ - + Style Z (Class A) Style Y (Class B) OUT4 OUT3 OUT2 OUT1 -NAC4+ -NAC3+ -NAC2+ -NAC1+ TB2 AUX TBL NO NC COM TB5 JP1 J3 JP2 JP3 AUX AUX + IN2IN2+ OUT1OUT1+ IN1IN1+ SYNC IN SYNC IN + TB4 Internal Trouble Contact HPF24S ZNAC-4 Option Module End-of-Line Resistor supplied with Control Module 1 2 3 4 5 6 7 8 9 10 SLC TT1111 TT1100 TT11 TT99 TT88 TT22 TT33 TT77 TT66 TTTT4545 NAC (steady, FACP no sync) 8 7 6 5 4 3 2 1 3 2 1 FACP NAC End-of-Line Resistor Temporal Bell Circuit 4 Temporal Bell Circuit 3 Horn/Strobe Circuit 2 Horn/Strobe Circuit 1 SW1 Switch Settings 1 & 2 = sync (any setting but OFF/OFF) 3 = OFF (master) 4 = OFF (no AC Fail reporting delay) 5 = ON 6 = OFF Split Temporal 7 = OFF (charger enabled) 8 = OFF (circuit 4 NAC) Control Module* *If the SLC device does not match the one in this figure, refer to the SLC manual wiring conversion charts for legacy and newer versions of the modules. Figure 5.3 Split Temporal Mode Application 24fsapp5tpH2.wmf 32 HPF24S Series Power Supplies - P/N 52751:F2 7/11/2014

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48

32
HPF24S Series Power Supplies —
P/N 52751:F2
7/11/2014
Applications
Split Temporal Mode of Operation
5.3
Split Temporal Mode of Operation
In this application, the power supply has been set as a master with two synchronized and two non-
synchronized outputs as determined by the Split Temporal mode feature.
Control Input #1 (TB4,
Terminals 3 & 4) is connected to an addressable control module
which will cause the synchronized
power supply output circuits 1 & 2 to turn on. Control Input #2 (TB4, Terminals 7 & 8) is con-
nected to an FACP Notification Appliance Circuit which is used to activate the power supply’s tem-
poral output circuits 3 & 4.
TB4
JP3
J3
TB5
TB2
JP1
JP2
OUT4
-NAC4+
OUT4
-NAC4+
OUT4
-NAC4+
OUT3
-NAC3+
OUT2
-NAC2+
OUT1
-NAC1+
AUX -
IN2-
IN2+
OUT1-
OUT1+
IN1-
IN1+
SYNC IN -
SYNC IN +
AUX +
NO NC
AUX TBL
COM
1
2
3
4
5
6
7
8
9
10
8
7
6
5
4
3
2
1
8
7
8
7
TB2
TB2
3
2
1
+
+
+
+
+
+
+
+
+
-
-
-
-
-
-
-
-
-
Figure 5.3
Split Temporal Mode Application
Style Z (Class A)
Style Y (Class B)
Temporal Bell Circuit 4
Temporal Bell Circuit 3
Horn/Strobe Circuit 2
Horn/Strobe Circuit 1
Use listed ELR
(4.7K
) to
terminate Style Y
(Class B) NAC
ELR not required for
Style Z (Class A) NAC
Note: All NACs are supervised and power-limited (Class 2)
ZNAC-4
Option Module
SW1 Switch Settings
1 & 2 = sync (any setting but
OFF/OFF)
3 = OFF (master)
4 = OFF (no AC Fail reporting delay)
5 = ON
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
Internal Trouble Contact
Split Temporal
FACP
Control Module*
End-of-Line
Resistor supplied
with Control Module
FACP NAC
End-of-Line
Resistor
Bells
Bells
SLC
24fsapp5tpH2.wmf
*If the SLC device does not match the one in this figure, refer to the SLC manual
wiring conversion charts for legacy and newer versions of the modules.
T11
T10
T9
T8
T7
T6
T1
T2
T3
T4
T5
HPF24S
NAC
(steady,
no sync)