LG ARUN096BT2 Installation Manual - Page 36

The amount of Refrigerant, Special condition

Page 36 highlights

x The amount of Refrigerant The calculation of the additional charge should take into account the length of pipe. A Product Charge(kg(lb)) B Additional charge (kg(lb)) = Total liquid pipe (m(ft.)): Ø22.2mm(7/8inch) x 0.354(kg/m) ¡ 0.237 lb/ft + Total liquid pipe (m(ft.)): Ø19.05mm(3/4inch) x 0.266(kg/m) ¡ 0.178 lb/ft + Total liquid pipe (m(ft.)): Ø15.88mm(5/8inch) x 0.173(kg/m) ¡ 0.116 lb/ft + Total liquid pipe (m(ft.)): Ø12.7mm(1/2inch) x 0.118(kg/m) ¡ 0.079 lb/ft + Total liquid pipe (m(ft.)): Ø9.52mm(3/8inch) x 0.061(kg/m) ¡ 0.041 lb/ft + Total liquid pipe (m(ft.)): Ø6.35mm(1/4inch) x 0.022(kg/m) ¡ 0.015 lb/ft + CF(kg(lb)) (Correction Factor) Total amount(kg(lb)) =A+ B CAUTION If a negative result is obtained from the calculation, no refrigerant needs to be added. Ex 10HP Outdoor Unit a : ø6.35(1/4), 10m(32.8ft) Indoor Unit b : ø6.35(1/4), 10m(32.8ft) A : ø9.52(3/8), 40m(131ft) c : ø6.35(1/4), 10m(32.8ft) B : ø9.52(3/8), 20m(65.6ft) d : ø6.35(1/4), 10m(32.8ft) C : ø9.52(3/8), 20m65.6ft) e : ø6.35(1/4), 10m(32.8ft) A C X c B3B d 4B b a 1B e 5B 2B Additional charge = A*0.041 + B*0.041 + C*0.041 +(a+b+c+d+e)*0.015 + CF = 40*0.041+20*0.041+65.6*0.041 + (32.8*5)*0.015 + (0)(CF) = 7.61(lb) x Special condition In case of the No. of CST TQ/RAC SE/ARTCOOL SF models are over than 50% of the connected indoor units when the total No. of connected indoor units are over than 50% of the max. connectable indoor units. Total amount(kg(lb)) = A + B + C s Additional refrigerant charging amount (kg) : = (A x + B x ß) - (AVG x ß) • A = Total No. of TQ,SE and SF Indoor units, = 0.5 • B = Total No. of except TQ,SE and SF Indoor units, ß = 0.3 • AVG = 50% of Max. No. of connectable Indoor units. Example) 1) Installation Information - Outdoor unit : 6HP - Total indoor units : 6 units (TQ 3 units, SE 2 units, BH 1 unit) 2) Information from PDB - Max. No. of connectable indoor units : 10 units - Calculated additional refrigerant amount = 2kg(0.91 lb) : 3) Indoor refrigerant charging amount = (5 units x 0.5+1 unit x 0.3) - (5 units x 0.3) = 1.3kg(0.59 lb) : Revised the total additional charging amount = = 2kg(0.91 lb) +1.3kg(0.59 lb) = 3.3kg(1.50 lb) 36 Outdoor Unit

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91

36
Outdoor Unit
The amount of Refrigerant
The calculation of the additional charge should take into account the length of pipe.
Product Charge(kg(lb))
Additional charge (kg(lb))
=
+
+
+
+
+
+
=
+
x 0.354(kg/m)
0.237 lb/ft
x 0.266(kg/m)
0.178 lb/ft
x 0.173(kg/m)
0.116 lb/ft
x 0.118(kg/m)
0.079 lb/ft
x 0.061(kg/m)
0.041 lb/ft
x 0.022(kg/m)
0.015 lb/ft
CF(kg(lb))
(Correction Factor)
If a negative result is obtained
from
the calculation, no refrigerant needs
to be added.
A
A
B
B
CAUTION
Total liquid pipe (m(ft.)): Ø22.2mm(7/8inch)
Total liquid pipe (m(ft.)): Ø19.05mm(3/4inch)
Total liquid pipe (m(ft.)): Ø15.88mm(5/8inch)
Total liquid pipe (m(ft.)): Ø12.7mm(1/2inch)
Total liquid pipe (m(ft.)): Ø9.52mm(3/8inch)
Total liquid pipe (m(ft.)): Ø6.35mm(1/4inch)
Total amount(kg(lb))
B
B
B
B
B
A
B
C
X
b
a
c
d
3
4
5
2
1
e
Outdoor Unit
Indoor Unit
A
: ø9.52(3/8), 40m(131ft)
B
: ø9.52(3/8), 20m(65.6ft)
C
: ø9.52(3/8), 20m65.6ft)
Ex
10HP
Additional charge = A*0.041 + B*0.041 + C*0.041
+(a+b+c+d+e)*0.015
+ CF
= 40*0.041+20*0.041+65.6*0.041
+ (32.8*5)*0.015 + (0)(CF)
= 7.61(lb)
a : ø6.35(1/4), 10m(32.8ft)
b : ø6.35(1/4), 10m(32.8ft)
c : ø6.35(1/4), 10m(32.8ft)
d : ø6.35(1/4), 10m(32.8ft)
e : ø6.35(1/4), 10m(32.8ft)
36
Outdoor Unit
Special condition
In case of the No. of CST TQ/RAC SE/ARTCOOL SF models are over than 50% of the connected
indoor units when the total No. of connected indoor units are over than 50% of the max. connectable
indoor units.
Additional refrigerant charging amount (kg)
:
= (A x
+ B x ß) - (AVG x ß)
• A = Total No. of TQ,SE and SF Indoor units,
= 0.5
• B = Total No. of except TQ,SE and SF Indoor units,
ß = 0.3
• AVG =
50% of Max. No. of connectable Indoor units.
Example)
1) Installation Information
- Outdoor unit : 6HP
- Total indoor units : 6 units
(TQ 3 units, SE 2 units, BH 1 unit)
2) Information from PDB
- Max. No. of connectable indoor units : 10 units
- Calculated additional refrigerant amount = 2kg(0.91 lb) :
3) Indoor refrigerant charging amount
= (5 units x 0.5+1 unit x 0.3) - (5 units x 0.3) = 1.3kg(0.59 lb) :
Revised the total additional charging amount =
= 2kg(0.91 lb) +1.3kg(0.59 lb)
= 3.3kg(1.50 lb)
+
=
Total amount(kg(lb))
A
B
+
C