The amount of Refrigerant, Special condition
View all LG ARUN096BT2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 36 highlights
x The amount of Refrigerant The calculation of the additional charge should take into account the length of pipe. A Product Charge(kg(lb)) B Additional charge (kg(lb)) = Total liquid pipe (m(ft.)): Ø22.2mm(7/8inch) x 0.354(kg/m) ¡ 0.237 lb/ft + Total liquid pipe (m(ft.)): Ø19.05mm(3/4inch) x 0.266(kg/m) ¡ 0.178 lb/ft + Total liquid pipe (m(ft.)): Ø15.88mm(5/8inch) x 0.173(kg/m) ¡ 0.116 lb/ft + Total liquid pipe (m(ft.)): Ø12.7mm(1/2inch) x 0.118(kg/m) ¡ 0.079 lb/ft + Total liquid pipe (m(ft.)): Ø9.52mm(3/8inch) x 0.061(kg/m) ¡ 0.041 lb/ft + Total liquid pipe (m(ft.)): Ø6.35mm(1/4inch) x 0.022(kg/m) ¡ 0.015 lb/ft + CF(kg(lb)) (Correction Factor) Total amount(kg(lb)) =A+ B CAUTION If a negative result is obtained from the calculation, no refrigerant needs to be added. Ex 10HP Outdoor Unit a : ø6.35(1/4), 10m(32.8ft) Indoor Unit b : ø6.35(1/4), 10m(32.8ft) A : ø9.52(3/8), 40m(131ft) c : ø6.35(1/4), 10m(32.8ft) B : ø9.52(3/8), 20m(65.6ft) d : ø6.35(1/4), 10m(32.8ft) C : ø9.52(3/8), 20m65.6ft) e : ø6.35(1/4), 10m(32.8ft) A C X c B3B d 4B b a 1B e 5B 2B Additional charge = A*0.041 + B*0.041 + C*0.041 +(a+b+c+d+e)*0.015 + CF = 40*0.041+20*0.041+65.6*0.041 + (32.8*5)*0.015 + (0)(CF) = 7.61(lb) x Special condition In case of the No. of CST TQ/RAC SE/ARTCOOL SF models are over than 50% of the connected indoor units when the total No. of connected indoor units are over than 50% of the max. connectable indoor units. Total amount(kg(lb)) = A + B + C s Additional refrigerant charging amount (kg) : = (A x + B x ß) - (AVG x ß) • A = Total No. of TQ,SE and SF Indoor units, = 0.5 • B = Total No. of except TQ,SE and SF Indoor units, ß = 0.3 • AVG = 50% of Max. No. of connectable Indoor units. Example) 1) Installation Information - Outdoor unit : 6HP - Total indoor units : 6 units (TQ 3 units, SE 2 units, BH 1 unit) 2) Information from PDB - Max. No. of connectable indoor units : 10 units - Calculated additional refrigerant amount = 2kg(0.91 lb) : 3) Indoor refrigerant charging amount = (5 units x 0.5+1 unit x 0.3) - (5 units x 0.3) = 1.3kg(0.59 lb) : Revised the total additional charging amount = = 2kg(0.91 lb) +1.3kg(0.59 lb) = 3.3kg(1.50 lb) 36 Outdoor Unit