LG ARUN096BT2 Installation Manual - Page 67
Group Number setting
View all LG ARUN096BT2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 67 highlights
ENGLISH Group Number setting Group Number setting for Indoor Units Electrical Wiring Confirm the power of whole system(Indoor Unit, Outdoor Unit) is OFF, otherwise turn off. The communication lines connected to INTERNET terminal should be connected to central control of Outdoor unti with care for their polarity( A ¡ A, B ¡ B ) Turn the whole system on. Set the group and Indoor Unit number with a wired remote control. To control several sets of Indoor Units into a group, set the group ID from 0 to F for this purpose. SODU B A Outdoor Units Terminal block on the main PCB IDU INTERNET DRY1 DRY2 GND 12V B A B A B(D) A(C) Group recognizing the simple central controller No.0 group (00~0F) No.1 group (10~1F) No.2 group (20~2F) No.3 group (30~3F) No.4 group (40~4F) No.5 group (50~5F) No.6 group (60~6F) No.7 group (70~7F) No.8 group (80~8F) No.9 group (90~9F) No. A group (A0~AF) No. B group (B0~BF) No. C group (C0~CF) No. D group (D0~DF) No. E group (E0~EF) No. F group (F0~FF) Installation Manual 67