LG ARUN096BT2 Installation Manual - Page 79
Self-Diagnosis Function
View all LG ARUN096BT2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 79 highlights
ENGLISH Test Run Self-Diagnosis Function Error Indicator • This function indicates types of failure in self-diagnosis and occurrence of failure for air condition. • Error mark is displayed on display window of indoor units and wired remote controller, and 7-segment LED of outdoor unit control board as shown in the table. • If more than two troubles occur simultaneously, lower number of error code is first displayed. • After error occurrence, if error is released, error LED is also released simultaneously. Error Display 1st,2nd LED of 7-segment indicates error number, 3rd LED indicates unit number. Ex) 211 : No.21 error of master unit 213 : No.21 error of slave 011 ¡ 051 : No.105 error of master unit Indoor unit related error Display Title Cause of Error 0 1 - Air temperature sensor of indoor unit Air temperature sensor of indoor unit is open or short 0 2 - Inlet pipe temperature sensor of indoor unit Inlet pipe temperature sensor of indoor unit is open or short 0 3 - Communication error : wired remote controller ↔ indoor unit Failing to receive wired remote controller signal in indoor unit PCB 0 4 - Drain pump 0 5 - Communication error : outdoor unit ↔ indoor unit 0 6 - Outlet pipe temperature sensor of indoor unit Malfunction of drain pump Failing to receive outdoor unit signal in indoor unit PCB Outlet pipe temperature sensor of indoor unit is open or short 0 7 - Different operation mode Operation mode between indoor unit and outdoor unit is different 0 9 - Serial No. In case when the serial number marked on EEPROM of Indoor unit is 0 or FFFFFF 1 0 - Poor fan motor operation Disconnecting the fan motor connector/Failure of indoor fan motor lock 1 1 - Communication error: indoor unit ¡ main PCB of outdoor. When the addressing signal doesn't respond for 3mins. suddenly, while the indoor unit gets the calling signal from the outdoor unit, 1 Master Outdoor Unit Inverter Compressor IPM Fault Master Outdoor Unit Inverter Compressor Drive IPM Fault 2 1 2 Slave1 Outdoor Unit Inverter Compressor IPM Fault Slave1 Outdoor Unit Inverter Compressor Drive IPM Fault 3 Slave2 Outdoor Unit Inverter Compressor IPM Fault Slave2 Outdoor Unit Inverter Compressor Drive IPM Fault Inverter Board Input Over 1 Current(RMS) of Master Outdoor Unit Master Outdoor Unit Inverter Board Input Current excess (RMS) Inverter Board Input Over Slave1 Outdoor Unit Inverter Board Input Current 2 2 2 Current(RMS) of Slave1 Outdoor excess (RMS) Unit Inverter Board Input Over 3 Current(RMS) of Slave2 Outdoor Unit Slave2 Outdoor Unit Inverter Board Input Current excess (RMS) Outdoor unit related error Installation Manual 79