LG ARUN096BT2 Installation Manual - Page 62
DIP switch setting
View all LG ARUN096BT2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 62 highlights
Electrical Wiring DIP switch setting s Checking according to dip switch setting 1. You can check the setting values of the main outdoor unit from the 7 segment LED. The dip switch setting should be changed when the power is OFF. 2. It checks whether the input is properly performed without the bad contact of the dip switch or not s Checking the setting of the Master unit The number is sequentially appeared at the 7 segment in 5 seconds after applying the power. This Number represents the setting condition.(For example, represents 3Ø 208/230V 20HP heat pump) Master model code ¡ Slave1 model code ¡ total capacity ¡ 2 ¡ 25 ¡ 140 1~255 : Master model code 1~255 : Master model code 1~255 : Master model code 5~48 HP : HP number (Sum of Master capacity and Slave capacity) No display : cooling only 2 : Heat pump 3: Sync 25 : Normal 140 : 3Ø 208/230V 160 : 3Ø 460V Example) 3Ø 208/230V 20HP heat pump 151 ¡ 151 ¡ 20 ¡ 2 ¡ 25 ¡ 140 CAUTION Product may not properly operate if the relevant DIP switch is not properly setup. Model Code 3Ø 208/230V Model Code 150 151 152 Unit (HP) 8 10 12 3Ø 460V Model Code 171 172 173 174 175 Unit (HP) 8 10 12 14 16 62 Outdoor Unit