LG ARUN096BT2 Installation Manual - Page 86
Slave2 Outdoor Unit Fan Inverter PCB Temperature is
View all LG ARUN096BT2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 86 highlights
Test Run Outdoor unit related error Display Title Master Outdoor Unit Constant 1 Speed Compressor Fault Slave1 Outdoor Unit Constant 1 7 3 2 Speed Compressor Fault Slave2 Outdoor Unit Constant 3 Speed Compressor Fault Excessive increase of Master 1 Outdoor Unit Fan PCB Heat Sink Temperature Excessive increase of Slave1 1 9 3 2 Outdoor Unit Fan PCB Heat Sink Temperature Excessive increase of Slave2 3 Outdoor Unit Fan PCB Heat Sink Temperature Master Outdoor Unit Fan PCB 1 Heat Sink Temperature Sensor Error Slave1 Outdoor Unit Fan PCB 1 9 4 2 Heat Sink Temperature Sensor Error Slave2 Outdoor Unit Fan PCB 3 Heat Sink Temperature Sensor Error Cause of Error Comp locking, Check Valve leakage, comp dielectric break down at Master Outdoor Unit Comp locking, Check Valve leakage, comp dielectric at Slave1 Outdoor Unit Comp locking, Check Valve leakage, comp dielectric at Slave2 Outdoor Unit Master Outdoor Unit Fan Inverter PCB Temperature is Over 95°C Slave1 Outdoor Unit Fan Inverter PCB Temperature is Over 95°C Slave2 Outdoor Unit Fan Inverter PCB Temperature is Over 95°C Master Outdoor Unit Fan PCB Heat Sink Temperature Sensor open or short Slave1 Outdoor Unit Fan PCB Heat Sink Temperature Sensor open or short Slave2 Outdoor Unit Fan PCB Heat Sink Temperature Sensor open or short 86 Outdoor Unit