LG ARUN096BT2 Installation Manual - Page 76
Outdoor Unit, Test Run
View all LG ARUN096BT2 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 76 highlights
Test Run CAUTION 1. Guaranteed Temperature range(Error occurs out of guaranteed temperature range) IDU : 20(68˚F)~32°C(90˚F) ODU : 10(50˚F)~38°C(100˚F) 2. Set IDU wired remote controller temperature sensor setting as 'IDU'. 3. Make certain that IDU doesn't run with thermo off mode during operation. [ Error contents about auto refrigerant charging function ] 1. : Temperature Range Error (In case that IDU or ODU is out of range) 2. : System Unstable Error (In case, After 45 min operating the system, it does not be stable) How to Cope with Result of Refrigerant checking 1. If the temperature is not in guaranteed Temperature range, the system will not execute Refrigerant checking and the system will be OFF. 2. Excess of Refrigerant(619) After remove the 20% of calculated total refrigerant, recharge the refrigerant by using Refrigerant Auto Charging Function. 3. Scarcity of Refrigerant(629) Charge the refrigerant by using Refrigerant Auto Charging Function. 4. Impossible to Judge(639) IF the system is not in order, check the other problem except refrigerant. 76 Outdoor Unit