Toshiba UT1A1A010C6 User Guide - Page 26
Free Run Mode, Diagnostic Tests, System Configuration
View all Toshiba UT1A1A010C6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 26 highlights
than a second and the on-line mode can be reactivated immediately. Switching back to online mode occurs when the input voltage exceeds ±10% (or ±15% selectable), when the input frequency exceeds ±3Hz, or when no input line is available. Although high efficiency is standard, the default operation is the on-line mode. From the LCD display panel, Bypass can be activated as required or On-line operation can be run permanently if preferred. 2.3 Free Run Mode Free run mode is a mode of operation in which the UPS outputs a pre-set frequency (50 or 60 Hz) regardless of the input frequency. The UPS operates in free run mode when the input frequency is outside of the selected input frequency range. When starting the UPS, the targeted frequency is 50 or 60 Hz ±0.25 Hz. 2.4 Diagnostic Tests When the UPS is started, a diagnostic test is executed automatically that checks the electronics and battery, and reports any problems on the LCD display. The advanced battery management system monitors the performance of the battery and will indicate if battery replacement is required. The battery management system tests the battery every 30 days of normal mode operation. A battery discharge test is performed and reports any problems on the LCD display. Except during the first 24 hours after startup while the UPS is in charging mode, diagnostic tests can be performed manually from the front panel when required. 2.5 System Configuration The UPS device and the internal backup battery make up the system. Depending on the site and load requirements of the installation, available options may be utilized to create a tailored solution. Planning a UPS system should include the following considerations: 4