5.5 Front Panel Settings Listed below are the default settings of the primary UPS parameters. Settings 1) O/P VOLT SET (output voltage set) Options 100/110/115/120/127 208/220/230/240 Vac 2) I/P FREQ SET (input frequency setting) 3) I/P BYPASS SET (input bypass setting) 4) FREE RUN SET +/- 2% +/- 5% +/- 7% +/- 10% +10% -15% +15% -20% ON/OFF 5) HE MODE SET ON/OFF 6) MANUAL BYPASS ON/OFF Default 120 V 230 V Remarks 120 V (FOR LV series) 230 V (FOR HV series) +/- 5% +10% -15% Input Frequency range in Free Run mode Input Voltage range when Bypass mode is on ON OFF OFF If ON, enable UPS runs on Asynchronous mode. For example: If input freq 55Hz output freq stays at 60Hz. If OFF, disable UPS runs on synchronous mode. For example: If input freq 55Hz, UPS will go to battery mode. If ON, enable UPS runs in High efficiency mode. The unit will be in bypass mode with 95% or higher efficiency. If OFF, the unit will be in the online mode with 85% efficiency. If ON, enable UPS switch to Bypass mode immediately. 12

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51

12
5.5
Front Panel Settings
Listed below are the default settings of the primary UPS parameters.
Settings
Options
Default
Remarks
1) O/P VOLT SET
(output voltage
set)
100/110/115/120/127
208/220/230/240 Vac
120 V
230 V
120 V (FOR LV series)
230 V (FOR HV series)
2) I/P FREQ SET
(input frequency
setting)
+/- 2%
+/- 5%
+/- 7%
+/- 5%
Input Frequency range in
Free Run mode
3) I/P BYPASS
SET
(input bypass
setting)
+/- 10%
+10% -15%
+15% -20%
+10%
-15%
Input Voltage range when
Bypass mode is on
4) FREE RUN
SET
ON/OFF
ON
If ON, enable UPS runs on
Asynchronous
mode.
For example:
If input freq 55Hz
output freq stays at 60Hz.
If OFF, disable UPS runs on
synchronous mode.
For example:
If input freq 55Hz,
UPS will go to battery mode.
5) HE MODE SET
ON/OFF
OFF
If ON, enable UPS runs in
High efficiency
mode.
The
unit will be in bypass mode
with
95% or higher
efficiency.
If OFF, the unit will be in the
online mode with 85%
efficiency.
6) MANUAL
BYPASS
ON/OFF
OFF
If ON, enable UPS switch to
Bypass mode immediately.