Toshiba UT1A1A010C6 User Guide - Page 28
Storage, Shipping
View all Toshiba UT1A1A010C6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 28 highlights
3. Storage Please adhere to the following instructions if the UPS is not installed when received: • Store the equipment in its original packing and shipping carton. • Store the unit in a temperature of 59 - 77 °F (15 - 25 °C). • Ensure that the equipment is fully protected from wet or damp areas and from moist air. In order to maintain the vitality of the batteries, ensure that the UPS is recharged every 6 months for at least 8 hours during storage. 4. Shipping The cold start function must be disabled before the UPS is shipped. Cold start applies power to the UPS output with no UPS input. This can pose a shock or fire hazard if the output terminals are shorted. Toshiba is not responsible for any resultant fire or damage if the cold start function is not disabled. Cold Start Disable Procedure: 1. Ensure the UPS is switched OFF. 2. Plug In AC Power. 3. Press and hold the Function Key while pressing the Enter key 3 times. 4. After a beep sounds, unplug the AC power cord and wait for UPS to shutdown automatically. ** Note: Cold start will be automatically re-enable when the UPS is plugged into commercial power and switched ON. Products that shipped after December 2007 include a cover over the ON/OFF Key to prevent accidentally pressing against the On/Off Button during shipping. Follow the above procedure to disable Cold Start and close the cover to prevent a fire hazard. 6