Toshiba UT1A1A010C6 User Guide - Page 43
UPS Manual Test, Interpreting UPS Messages, Audible Alarms, 10 Silencing an Alarm
View all Toshiba UT1A1A010C6 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 43 highlights
7.7 UPS Manual Test Manual UPS and Battery tests may be performed from the UPS configuration screen. Tests may be performed when the battery is not being charged. To run the battery test scroll to the "Manual Bat Test" parameter press the Enter button twice. ** Note: In order for the UPS to operate normally, Manual Bypass should always be set to OFF because the load will not be protected by the unit when Manual Bypass is ON. *** Note: Turn off the UPS and keep the AC power on to use the Generator function. (go to normal mode for \Generator\OFF). 7.8 Interpreting UPS Messages Troubleshooting procedures described here provide instructions to be used to isolate UPS malfunctions. Start the troubleshooting procedure in the event of a control panel alarm. 7.9 Audible Alarms • While operating on battery power (ON BAT LED is on) the UPS will beep once at 5-second intervals. • While operating on battery power and the battery power is low (ON BAT LED is flashing) the UPS will beep twice at 5-second intervals. • In the event of an internal fault with an active alarm (ALARM LED is on), the UPS will provide a constant audible alarm and display an error message on the LCD display. • While operating in the Bypass mode (BYPASS LED is on) the UPS will not beep. 7.10 Silencing an Alarm With the exception of a LOW BATTERY Alarm, pressing any of the front panel buttons will turn off the alarm. Select Silent Alarm Mode to disable all audible alarms. 21