Power requirements for the base enclosure Power requirements will vary depending on system configuration, loading, and environmental conditions. The table below describes the maximum expected power draw. To estimate power consumption values for your specific environment, go to https://powercalculator.dellemc.com/. Table 4. Power requirements Requirement 1000T/1000X/ 3000T/3000X/ 5000T/5200T 5000X 1200T 3200T 7000T/7000X Maximum input power 240 VAC ± 10%, single phase For 100-120V, a customer-supplied step-up transformer is required 9000T/9000X/ 9200T AC Line Current 8.1 A (operating maximum at 200 VAC) 8.1 A 9.0 A 9.0 A 9.3 A 10.4 A Power Consumption (operating maximum at 200 VAC) 1629.6 VA (1597 W) 1629.6 VA (1597 W) 1792.9 VA (1757 W) 1792.9 VA (1757 W) 1868.4 VA (1831 W) 2088.8 VA (2047 W) Heat Dissipation 5.74 x 106 J/hr, (operating (5,449 Btu/hr) maximum) 5.74 x 106 J/hr, (5,449 Btu/hr) 6.32 x 106 J/hr, (5,995 Btu/hr) 6.32 x 106 J/hr, (5,995 Btu/hr) 6.59 x 106 J/hr, (6,248 Btu/hr) 7.37 x 106 J/hr, (6,985 Btu/hr) AC Inlet type IEC320-C14 or IEC320-C20 appliance coupler per power zone IEC320-C20 appliance coupler per power zone Normal input frequency 47 Hz-63 Hz Maximum inrush current 45 Apk "cold" per line cord at any line voltage AC protection 20 A fuse on each power supply, single line Ride-through time 10 ms min Current sharing ± 5 percent of full load, between power supplies Startup Surge Current 120 Apk "hot" per line cord, at any line voltage Table 5. High ambient temperature shutdown Ambient temperature Hardware fault Above 45° C (113° F) None Above 50° C (122° F) None Any Three hottest drives have average temperature of 50° C (122° F) Any Two fans fault Consequence Non-critical warning generated. Critical alert generated. System shuts down after five minute timer expires. If the temperature returns to less than 45° C (113° F) , the system powers on. System shuts down after five minute timer expires. System shuts down after five minute timer expires. Site Planning 11

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34

Power requirements for the base enclosure
Power requirements will vary depending on system configuration, loading, and environmental conditions. The table below
describes the maximum expected power draw. To estimate power consumption values for your specific environment, go to
.
Table 4. Power requirements
Requirement
1000T/1000X/
1200T
3000T/3000X/
3200T
5000T/5200T
5000X
7000T/7000X
9000T/9000X/
9200T
Maximum input
power
240 VAC ± 10%, single phase
For 100-120V, a customer-supplied step-up transformer is required
AC Line Current
(operating
maximum at 200
VAC)
8.1 A
8.1 A
9.0 A
9.0 A
9.3 A
10.4 A
Power
Consumption
(operating
maximum at 200
VAC)
1629.6 VA (1597
W)
1629.6 VA (1597
W)
1792.9 VA (1757
W)
1792.9 VA (1757
W)
1868.4 VA (1831
W)
2088.8 VA
(2047 W)
Heat Dissipation
(operating
maximum)
5.74 x 10
6
J/hr,
(5,449 Btu/hr)
5.74 x 10
6
J/hr,
(5,449 Btu/hr)
6.32 x 10
6
J/hr,
(5,995 Btu/hr)
6.32 x 10
6
J/hr,
(5,995 Btu/hr)
6.59 x 10
6
J/hr,
(6,248 Btu/hr)
7.37 x 10
6
J/hr,
(6,985 Btu/hr)
AC Inlet type
IEC320-C14 or IEC320-C20 appliance coupler per
power zone
IEC320-C20 appliance coupler per power zone
Normal input
frequency
47 Hz–63 Hz
Maximum inrush
current
45 Apk "cold" per line cord at any line voltage
AC protection
20 A fuse on each power supply, single line
Ride-through
time
10 ms min
Current sharing
± 5 percent of full load, between power supplies
Startup Surge
Current
120 Apk "hot" per line cord, at any line voltage
Table 5. High ambient temperature shutdown
Ambient temperature
Hardware fault
Consequence
Above 45° C (113° F)
None
Non-critical warning generated.
Above 50° C (122° F)
None
Critical alert generated. System
shuts down after five minute timer
expires. If the temperature returns
to less than 45° C (113° F) , the
system powers on.
Any
Three hottest drives have average temperature of
50° C (122° F)
System shuts down after five
minute timer expires.
Any
Two fans fault
System shuts down after five
minute timer expires.
Site Planning
11