Hayward Pro Logic® Models: PL-PS-4 PL-PS-8 PL-PS-16 PL-PS-16V Installatio - Page 21
Pro Logic Output, VSP Address - pro logic 2
View all Hayward Pro Logic® manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 21 highlights
STA-RITE Heater 1. Turn power off to heater. 2. Remove upper jacket and open the control box. 3. Remove the jumper for the "fireman's switch. 4. Wire to the Pro Logic using wire rated for 105°C minimum. Fireman's Switch Operating 'Control Terminal Board STA-RITE Hayward Variable Speed Pump (VSP) Wiring and Address Setting Refer to your TriStar or EcoStar manual(s) for proper low voltage communication wiring between the Pro Logic and the Hayward Variable Speed Pump. A pump address must be configured for each VSP used in the system. This address is entered into the VSP's configuration menu. Refer to the table below to determine which address to use for your specific pump and Pro Logic. Select the proper address based on which output will be used and the model VSP you are configuring. Pro Logic Output This is the output used to control the VSP. Note that the VSP should be wired to this output's corresponding relay. VSP Address This is the name that should be selected under "Set COMM bus address" (EcoStar) or "*H.Comm ADDR." (TriStar) within the VSP's Configuration Menu. FILTER - all Pro Logic models "001" - Tristar "Pool Filter" - EcoStar AUX1 - all Pro Logic models Dual Equipment Spa Filter - all models "002" - Tristar "Aux1 / Spa Filter" - EcoStar LIGHTS - all Pro Logic models "Lights Button" - EcoStar only AUX2 - all Pro Logic models AUX3-AUX6 - PS8 & PS16 models AUX7-AUX14 - PS16 models Aux2-Aux14 - EcoStar only (use same as Pro Logic Output) 18