Hayward Universal H-Series Low NOx Service/Installation: H150FDN H200FDN H25 - Page 14

All Air Supply From Inside The Building, All Air Supply From Outdoors - heater - natural gas

Page 14 highlights

14 (A) All Air Supply From Inside the Building: The confined space shall be provided with 2 permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space (a space whose volume is not less than 50 cubic feet per 1,000 btu/hr). The total input of all gas utilization equipment installed in the combined space shall be considered in making the determination. Each opening shall have a minimum free area of 1 square inch per 1,000 btu/hr of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches. See Table 4. One opening shall be within 12 inches of the top and and one within 12 inches of the bottom of the enclosure. (B) All Air Supply From Outdoors: Figure 9 The confined space shall be provided with 2 permanent openings, once commencing within 12 inches of the bottom Below-BGelorwo-GuronuFdnigdu((rPPeit9)iItn)staIlnlatsiotnallation of the enclosure. The opening shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors. Ventilation Air Vent Cap Ground Level Combustion Air 1. When communicating with the outdoors (either di- rectly or through vertical ducts), each opening shall have a minimum free area of 1 square inch per 4,000 Rise of 1 inch per foot Air Duct from Ground to Base btu/hr of total input rating of all equipment in the enclosure. See Table 4. 2. When communicating with the outdoors through hori- Drip Tee zontal ducts, each opening shall have a minimum free area of 1 square inch per 2,000 btu/hr of total input Gas Cock rating of all equipment in the enclosure. See Table 4. 3. When ducts are used, they shall be of the same cross- sectional area as the free area of the openings to which they connect. The minimum dimension of rect- Sediment Trap Level Flooring or Slab angular air ducts shall not be less than 3 inches. Table 4: Combustion and Ventilation Air Requirements 4. When installing a heater below Free Area per Btu Total Input Combustion Air Free Ventilation Air Free ground (in a pit), combustion and ventilation air openings must be provided as shown in Figure 9. Requirement 1 sq. in. per 1,000 btu/hr (paragraph A) (btu/hr) 150,000 200,000 250,000 Area Required (sq. in.) 150 200 250 Area Required (sq. in.) 150 200 250 Each opening shall have a minimum free area of 1 square inch per 300,000 300 300 350,000 350 350 400,000 400 400 250 btu/hr or total input rating of all equipment in the pit. See Table 1 sq. in. per 2,000 btu/hr (paragraph B-2) 150,000 200,000 250,000 75 100 125 75 100 125 4. Below-ground (pit) installations 300,000 150 150 must be natural gas only. 350,000 175 175 400,000 200 200 For more detailed methods of providing air for combustion and ventilation, 1 sq. in. per 4,000 btu/hr (paragraph B-1) 150,000 200,000 250,000 300,000 37.5 50 62.5 75 37.5 50 62.5 75 refer to the latest edition of the National 350,000 87.5 87.5 Fuel Gas Code (ANSI Z223.1/NFPA 54). 1 sq. in. per 250 btu/hr 400,000 150,000 100 600 100 600 (paragraph B-4) 200,000 250,000 800 1000 800 1000 300,000 1200 1200 350,000 1400 1400 400,000 1600 1600 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS Pomona, CA Clemmons, NC Nashville, TN Tel: 908-351-5400 www.haywardpool.com

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64

Pomona, CA Clemmons, NC Nashville, TN
Tel: 908-351-5400
www.haywardpool.com
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
14
(A)
ALL AIR SUPPLy FROM INSIDE THE BUILDING:
The confined space shall be provided with 2 permanent openings communicating directly with an addi-
tional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an uncon-
fined space (a space whose volume is not less than 50 cubic feet per 1,000 btu/hr).
The total input of all gas
utilization equipment installed in the combined space shall be considered in making the determination.
Each
opening shall have a minimum free area of 1 square inch per 1,000 btu/hr of the total input rating of all gas
utilization equipment in the confined space, but not less than 100 square inches.
See Table 4.
One opening
shall be within 12 inches of the top and and one within 12 inches of the bottom of the enclosure.
(B)
ALL AIR SUPPLy FROM OUTDOORS:
The confined space shall be provided with 2 permanent
openings, once commencing within 12 inches of the bottom
of the enclosure. The opening shall communicate directly,
or by ducts, with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors.
1. When communicating with the outdoors (either di-
rectly or through vertical ducts), each opening shall
have a minimum free area of 1 square inch per 4,000
btu/hr of total input rating of all equipment in the
enclosure. See Table 4.
2. When communicating with the outdoors through hori-
zontal ducts, each opening shall have a minimum free
area of 1 square inch per 2,000 btu/hr of total input
rating of all equipment in the enclosure. See Table 4.
3.
When ducts are used, they shall be of the same cross-
sectional area as the free area of the openings to
which they connect. The minimum dimension of rect-
angular air ducts shall not be less
than 3 inches.
4. When installing a heater below
ground (in a pit), combustion and
ventilation air openings must be
provided as shown in Figure 9.
Each opening shall have a mini-
mum free area of 1 square inch per
250 btu/hr or total input rating of
all equipment in the pit.
See Table
4.
Below-ground (pit) installations
must be natural gas only.
For more detailed methods of provid-
ing air for combustion and ventilation,
refer to the latest edition of the National
Fuel Gas Code (ANSI Z223.1/NFPA 54).
Table 4: Combustion and Ventilation Air Requirements
Free Area per Btu
Requirement
Total Input
(btu/hr)
Combustion Air Free
Area Required (sq. in.)
Ventilation Air Free
Area Required (sq. in.)
1 sq. in. per 1,000 btu/hr
(paragraph A)
150,000
150
150
200,000
200
200
250,000
250
250
300,000
300
300
350,000
350
350
400,000
400
400
1 sq. in. per 2,000 btu/hr
(paragraph B-2)
150,000
75
75
200,000
100
100
250,000
125
125
300,000
150
150
350,000
175
175
400,000
200
200
1 sq. in. per 4,000 btu/hr
(paragraph B-1)
150,000
37.5
37.5
200,000
50
50
250,000
62.5
62.5
300,000
75
75
350,000
87.5
87.5
400,000
100
100
1 sq. in. per 250 btu/hr
(paragraph B-4)
150,000
600
600
200,000
800
800
250,000
1000
1000
300,000
1200
1200
350,000
1400
1400
400,000
1600
1600
Figure 9
Below-Ground (Pit) Installation
Ground Level
Ventilation
Air
Combustion
Air
Air Duct from
Ground to Base
Drip Tee
Gas Cock
Sediment Trap
Level Flooring
or Slab
Rise of 1 inch
per foot
Vent Cap