HP LH4r HP Netserver LH 3000 Rack Cabling Guide

HP LH4r - NetServer - 256 MB RAM Manual

HP LH4r manual content summary:

  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 1
    HP NetServer LH 3000r Rack Cabling Reference Guide
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 2
    . Hewlett-Packard shall not be liable for errors contained herein or for incidental or consequential damages for the use or reliability of its software on equipment that is not furnished by Hewlett Corporation. Hewlett-Packard Company Network Server Division Technical Communications/MS 45SLE
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 3
    Cable Lengths........ 29 Cooling Requirements for the LH 3000r 30 3 Procedure for Connecting and Routing Cables to the LH 3000r 31 Step 1: Prepare to Cable the HP NetServer LH 3000r 31 Assess How Components Will be Connected to the Server 31 Attach Cable Guide to Rack Column 31 Mount the Cable
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 4
    to Other Components 37 Step 3: Cable the LH 3000r for Power 37 Attaching Server and Component Power Cables 37 Determining and Balancing Managing and Routing Cables 51 Using the Cable Management Arm and the Cable Guides 51 Route and Tie Cables into the Management Arm 51 Step 5: Powering
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 5
    to use in this process, see Appendix A. For instructions on how to install the HP NetServer LH 3000r in a rack, consult the Installation Road Map shipped with your rack or the Installation Guide shipped with your NetServer unit. NOTE For instructions on how to assemble other components in a rack
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 6
    for Cabling the HP NetServer LH 3000r Figure 1-1. The HP NetServer LH 3000r Site Preparation You may want to copy and use the site preparation checklist in this section (Table 1-1). Doing so before you begin to install and cable the NetServer may reveal actions you can take to support your success
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 7
    HP NetServer General Guidelines Logical and physical network design provided Server configuration parameters determined Disk partition and directory structure determined Required incoming power and data cabling in place Working LAN, one working client, one working printer available (if integrating
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 8
    Chapter 1 Preparation for Cabling the HP NetServer LH 3000r Table 1-1. Site Preparation Checklist (Continued) Environment and Space Requirements Must meet OSHA, local code, and HP specifications for safety and supportability (3 feet minimum access in front and rear of electrical cabinets) Side
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 9
    Chapter 1 Preparation for Cabling the HP NetServer LH 3000r standby mode. Inrush current is much greater than the server's normal operating needs. Generally, your external AC power source can handle the inrush current. However, if you install several HP NetServers on one circuit, precautions are
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 10
    HP NetServer LH and telephone cords when you service or install components. Prevent Damage a static-dissipating work surface connected to the server chassis when handling printed circuit boards, memory devices in the system. Follow instructions in the section entitled "Power Up Sequence" at the
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 11
    without help. Also, remove power supplies and hard disk drives to minimize the amount of weight to be lifted. Compare the order documents to the packing list or to a list of boxes received. Check to see that all parts are present. Unpack the HP NetServer and external storage and tape backup units
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 12
    Cabling the HP NetServer LH 3000r 3. more people and the proper equipment to move the rack enclosure, server, mass storage units, and other components. Stage cartons a few people are required for this step. 1. Follow any pictorial instructions on the outside of the shipping container to unbox the
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 13
    Chapter 1 Preparation for Cabling the HP NetServer LH 3000r WARNING When equipment is mounted on slides, them (from the bottom of the rack upward). Each package contains rack installation instructions or a user guide. NOTE If an Uninterruptible Power Supply (UPS) is included, plug it in as
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 14
    HP NetServer LH 3000r NOTE Older racks (with the words "HP Systems" on the nameplate) may require that enclosures to be tied together before any components are mounted inside them. To avoid problems install it following instructions which accompany the unit. NOTE Most HP NetServers have an
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 15
    site, to regenerate it. 2. Rack-optimized HP NetServers and mass storage units have instructions in their user or installation guides for mounting the units in the rack enclosure. For other servers and storage units, rack mounting instructions are included with optional rack-mount kits, if available
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 16
    connected and managed: Prepare to Cable the HP NetServer LH 3000r • Determine which components will be connected to each server. • Attach Cable Guides to the rack column. See instructions included with Cable Guides. • Attach Cable Management Arm to rear of server and to the rack column. 12
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 17
    1 Preparation for Cabling the HP NetServer LH 3000r • Determine configurations for and mount the PDU (Power Distribution Unit or Units). Connect the LH 3000r Data Cables to Peripheral Components • Plan where data connections are to be made. • Attach data cables to the server. Mark the ends of
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 18
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 19
    the worldwide web. Enter the following URL in your browser: www.hp.com/go/netserver At that Web site, search for "configuration tools". Look for Rack Configuration, Rack Assistant, and Order Assistant. You can read about the tools or download copies for installation. These tools can be used to plan
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 20
    UPS) and distribution (PDU) components are available to support these configurations. A Redundant Switch is also available. Details of power considerations for the HP NetServer LH 3000r include: ◊ the appropriate power cord(s) for each server is (are) shipped according to voltage requirements; refer
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 21
    and receptacles for the rack power supply subsystems for the HP NetServer LH 3000r. Table 2-1. UPS Models and Power Ratings Uninterruptible in Volt Amps of each component and connect no more than those the UPS supports. Note 2. Also ensure UPS Wattage rating is not exceeded. Add power in Watts of
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 22
    Rack Cabling References Table 2-2. LH 3000r Plugs and Receptacles Reference LH 3000r Jumper Cord RackStorage/12 NS2200RMI3U or NS3000RMI3U SU044-1, C20 inputs, country-specific C19 cords, and E7804A, 4 m, C20 to C19 cord to PDU SU044-1, C20 inputs, country-specific C19 cords, and E7804A, 4 m C20
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 23
    UPS when this switch is used. Power Distribution Units Three types of Power Distribution Units (PDU) are currently available for the LH 3000r, as follows: ◊ The 120 VAC PDU (HP product number E7675A) fits either horizontally between the columns of the rack or vertically along the outside edge of the
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 24
    the door hinges. Table 2-3. PDU Placement is Not Recommended behind These Units HP Product Name HP NetServer LH 3000r and LC 2000r HP NetServer LXr 8000 and LXr 8500 HP NetServer LH 3r and LH 4r HP FiberChannel 30 HP NetServer Rack Storage/12 or /12FC Can PDU Be Mounted Behind? Horizontal Mounting
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 25
    , Power Cord Separately Orderable Figure 2-1. PDU Configurations The 200/240 VAC, wide-range Power Distribution Unit (PDU) can be mounted in several configurations with the LH 3000r. One of these configurations is shown in Figure 2-2. Others are listed and illustrated throughout Chapter 3. 21
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 26
    orient the PDU vertically or horizontally. Horizontal Mounting of Two PDUs in a Fully Utilized Rack Cable Guides Mounted on the Column Opposite Door Hinges Examples of Data Cable Routes from Server to Connectors on Other Components 100 - 120 VAC WideRange 16-Amp, Power Distribution Unit, Installed
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 27
    Chapter 2 Rack Cabling References Guidelines for Powering the LH 3000r in a Rack Four Possible 200/240 16-amp PDU is supplied for each Uninterruptible Power Supply (UPS) in a rack. 4. (a) When several HP Rack Storage/12 or Rack Storage/12FC units are in the same rack, use of two wide-range 16-
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 28
    Table 2-5. Receptacles Needed for Units Component Receptacles Required HP NetServer LH 3000r HP Rack Storage/12 one1 for each set of two requirements of the common rack mounted devices. Rack configuration utilities available from HP can help you plan the layout of your rack. Full parts lists
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 29
    Notes 1, 2, 3) HP NetServer LC 2000r HP NetServer LH 3000r HP NetServer LH 6000r HP NetServer LT 6000r HP NetServer LPr HP NetServer LXr 8000 and LXr 8500 HP NetServer LH 4r HP NetServer LH 3r HP NetServer LXr Pro8 HP NetServer LXr Pro HP Fibre Channel Hub D6976A HP Rack Storage/12FC HP Rack Storage
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 30
    Notes 1, 2, 3) HP NetServer LC 2000r HP NetServer LH 3000r HP NetServer LH 6000r HP NetServer LT 6000r HP NetServer LPr HP NetServer LXr 8000 and LXr 8500 HP NetServer LH 4r HP NetServer LH 3r HP NetServer LXr Pro8 HP NetServer LXr Pro HP Fibre Channel Hub D6976A HP Rack Storage/12FC HP Rack Storage
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 31
    (Notes 1, 2, 3) HP NetServer LC 2000r HP NetServer LH 3000r HP NetServer LH 6000r HP NetServer LT 6000r HP NetServer LPr HP NetServer LXr 8000 and LXr 85004 HP NetServer LH 4r HP NetServer LH 3r HP NetServer LXr Pro8 HP NetServer LXr Pro HP Fibre Channel Hub D6976A HP Rack Storage/12FC HP Rack
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 32
    Notes 1, 2, 3) HP NetServer LC 2000r HP NetServer LH 3000r HP NetServer LH 6000r HP NetServer LT 6000r HP NetServer LPr HP NetServer LXr 8000 and 85004 HP NetServer LH 4r HP NetServer LH 3r HP NetServer LXr Pro8 HP NetServer LXr Pro HP Fibre Channel Hub D6976A HP Rack Storage/12FC HP Rack Storage/12
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 33
    positioned and cables are routed so that the HP NetServer can be extended for service by trained personnel • power supplies and distribution server. And this in turn depends on Cable Guide placement. The left side is recommended for mounting of the Cable Management Arm and Cable Guides. • Cable Guide
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 34
    41 and 95 degrees F, 5 - 35 degrees C. Remember that ambient temperatures may be lower than the temperature inside the server. Because of the heat generated by the HP NetServer LH 3000r, both the front and rear doors of the rack must have perforated surfaces. (Alternatively, both front and rear
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 35
    the rack column. Mount the Cable Management Arm The HP NetServer LH 3000r includes a Cable Management Arm. Mount the arm by following the instructions in the HP NetServer LH 3000/3000r Installation Guide which accompanies your unit. Cable routing details are included in the section of this chapter
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 36
    Rack Storage/12" shows a set-up you might assemble before running HP NetServer Navigator to configure your server. Figure 3-2 shows a similar set-up for the Rack Storage/12FC. See the HP NetServer LH 3000/3000r Installation Guide for more information on setting up the system. CAUTION Cables with
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 37
    Rack Storage/12 Dashed Lines Indicate Dual Bus Configured Storage Figure 3-1. Overview of Data Cabling of the HP NetServer LH 3000r to an HP Rack Storage/12 NOTE Figure 3-1 shows an HP Console Switch, which is not necessary for configuring the system, but is shown for informational purposes
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 38
    3000r Figure 3-2 shows an HP NetServer LH 3000r connected in Dual Active Mode to a Rack Storage/12FC. HP 6-Port Hub with GBICs HP NetServer LH 3000r HP Rack Storage/12FC with GBICs HP Rack Storage/12 HP Rack Storage/12 Figure 3-2. Overview of Data Cabling of the HP NetServer LH 3000r to the Rack
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 39
    Procedure for Connecting and Routing Cables to the LH 3000r NOTE The configuration in Figure 3-2 requires on data cabling with the Rack Storage/12FC, see the HP Rack Storage/12 FC Installation Guide. Attach Data Cables to the Server 1. Locate SCSI connections, label both ends of the SCSI
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 40
    View of Rack Figure 3-3. Connecting the Data Cables between the LH 3000r and Rack Storage/12FC 2. Locate any network and remote management connections from hubs, routers and other sources and connect their cables to corresponding server connectors. 3. Locate the cable that will attach the serial
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 41
    LH 3000r and monitor for more than one server, attach the cables for the HP Console Switch to the server ports for video, mouse, and keyboard ports. Check Whether Cable Lengths Limit Distances between the Server Attaching Server and Component Power Cables 1. Make sure any manually switchable device
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 42
    Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r 4. For the sake of easy access to the rear of each component, route the associated power cords within chained 10-amp PDU and any other components, does not exceed 16 amperes. Add more PDU-UPS circuits to support higher loads. 38
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 43
    Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Figure 3-4. Power Connection Locations on a Typical Rack (Rear View) 100/120 VAC Rack Power Configurations The 120 VAC PDU power configurations are detailed in
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 44
    3 Procedure for Connecting and Routing Cables to the LH 3000r Connecting the PDU 120 VAC Configuration The Power Breakers." If your electrical system has the capacity to power the components, plug the HP NetServer LC 2000r and mass data storage units into NEMA 5-15 receptacles using the 90 inch
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 45
    and Routing Cables to the LH 3000r Table 3-1. 120 VAC Components Component1 Model PDU HP NetServer LH 3000r E7675A D8230A, 533 MHz, 512 MB D8238A, 600 MHz, 256 MB D8246B, 667 MHz, 256 MB Power (VA) N/A 531 Power (W) N/A 525 Current (A)2 max 16 4.5 HP NetServer Rack Storage/12 is D5989A
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 46
    Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Recommended 100-120 VAC Power Configuration HP NetServer LH 3000r Jumper Cables NEMA 5-15P to IEC 320 C-14 Mass Storage Unit Uninteruptible Power Supply NEMA 5-20P Detachable Cord NEMA 5-20P to IEC 320 C-20
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 47
    Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Figure 3-5 shows a UPS connected to the power grid the 208 VAC case, without a UPS, make sure your power system has the capacity to support the power and current needs of the components you will power. (See the section entitled "
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 48
    Table 3-2. 208 VAC Components Component1 Model 208 VAC PDU HP NetServer LH 3000r E7671A or E7672A D8230A, 533 MHz, 512 MB D8238A, 600 MHz, 256 MB D8246B, 667 MHz, 256 MB Power (VA) N/A 516 Power (W) N/A 506 Current (A)2 max 16 2.5 HP NetServer Rack Storage/12 is D5989A 522 512 2.6 Mass
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 49
    Procedure for Connecting and Routing Cables to the LH 3000r Recommended 208 VAC Power Configuration for the LH 3000r HP NetServer LH 3000r Uninterruptible Power Supply Captive L6-20P Cord Rack Mass Storage Unit Jumper Cable Supplied with NetServer Jumper Cables Supplied with Mass Storage Units
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 50
    Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r 230/240V PDU Rack Power Configurations Configurations for the 230/240 VAC, PDU options are shown in the text below, Table 3-3, and Figure 3-7. 230/
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 51
    VAC PDU Power and Current Component1 200/240 VAC PDU HP NetServer LH 3000r Model E7671A or E7672A D8230A, 533 MHz, 512 MB D8238A, 600 MHz, 256 MB D8246B, 667 MHz, 256 MB Power (VA) N/A 514 Power (W) N/A Current (A)2 max 16 504 2.3 HP NetServer Rack Storage/12 is D5989A 518 507 2.3 Mass
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 52
    Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Recommended 230/240 VAC LH 3000r Configuration HP NetServer LH 3000r Uninterruptible Power Supply Mass Storage Unit Jumper Cable Supplied with NetServer Jumper Cables Supplied with Mass Storage Units Captive Unterminated
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 53
    3 Procedure for Connecting and Routing Cables to the LH 3000r Redundant Power Configuration Dual Power Supply Example A power two PDUs. Figure 3-8 shows a dual power cabling example. This example shows two LH 3000r units powered by two PDUs and two UPS units. Plugging each UPS into a different
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 54
    in Figure 3-9. For this example, one 41EIA Unit Rack (a 2 meter HP Systems or HP System/E rack) is completely filled with power supplies, servers, and storage units. Two mass storage units "sandwich" each NetServer. Branch Circuit A Branch Circuit B Figure 3-9. High Density Configuration, Block
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 55
    mounting the cable management arm to the rear of the LH 3000r and to the HP Rack Systems unit are located in the rack mount chapter in the installation guide. The instructions below assume you have already mounted the arm. 1. Begin with the HP NetServer LH 3000r pushed all the way into the rack, and
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 56
    and Routing Cables to the LH 3000r A. Begin with the Server all the way in. B. Plug power and data cables into the back of the Server. F. Dress cables through the fingers of the Cable Guide. E. Determine whether to in the cable arm using the hook-and-loop cables supplied with the NetServer. 52
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 57
    Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r WARNING Before sliding the HP NetServer LH 3000r out of the rack, make sure you extend the anti-tip you have enough cable before routing cables through the Cable Guide. Figure 3-11. Extend the Server to Adjust Cable Lengths 53
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 58
    properly warned. No specific order is necessary when powering off rack-optimized servers and associated components. However, to do so in an orderly way, you should bring down the operating system, then power off peripherals, then turn off servers. WARNING The HP NetServer LH 3000r is connected to
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 59
    Guides, and follow instructions in the HP NetServer LH 3000/3000r Installation Guide to mount Cable Management Arms. Attach data cables to the HP NetServer, and the Cable Guides, and tie wrap them in place, if necessary. Power up components and then the server, following instructions in Chapter 3. 55
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 60
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 61
    B Considerations in Mounting the Redundant Switch A redundant switch is available from American Power Conversion Corporation (APC) for use in rack installations. Redundant switches can be used to enhance the reliability of rack power systems. This switch can be used with or without a rack-installed
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 62
    -1. Components for Use with the Redundant Switch and the LH 3000r Item APC Redundant Switch Model No. Power Cord from 044-1 2 Detachable Power Cords, Country Specific NS3000RMI3U or NS2200RMI3U2 E7804A, 4m, C20 to C19 2 Detachable Power Cords, Country Specific Not Used Not Used Not Used E7804A
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 63
    Appendix B Considerations in Mounting the Redundant Switch Figure B-1. 120 VAC Configuration of Redundant Switch between UPS and Branch Circuit 59
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 64
    Appendix B Considerations in Mounting the Redundant Switch Figure B-2. 120 VAC Configuration of Redundant Switch between PDU and Branch Circuit Note that switches of 200/208 and 230/240 VAC can be mounted in the same way as the 120 VAC models shown. See Table B-1. 60
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 65
    , 10 floor preparation checklist, 3 H hardware configuration preparation checklist, 4 high density configuration, 50 HP Console Switch use with LH 3000r, 32 HP NetServer LH 3000r cords, plugs, and receptacles, 17 voltages, 16 HP Rack Assistant, 29 M multiple rack bays tie together kit, 9 O operating
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 66
    procedure, 37 Power Distribution ensure the PDU is mounted, 32 Power Distribution Unit 120 VAC, 16 amp, 19 208 VAC illustration, 42, 45 208 VAC, LH 3000r configuration, 43 208/240 VAC, 10 amp extension, 19 208/240 VAC, 16 amp, 19 230/240 VAC illustration, 46, 48 configuration guidelines, 23
  • HP LH4r | HP Netserver LH 3000 Rack Cabling Guide - Page 67
    space requirements checklist, 4 system parameters checklist, 4 T turn on power, 54 U Uninterruptible Power Supply installation, 10 plug in early to charge batteries, 9 unpacking components, 9 Index rack enclosure, 8 UPS. See Uninteruptible Power Supply. See Uninterruptible Power Supply UPS or
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67

HP NetServer LH 3000r
Rack Cabling Reference Guide