HP LH4r HP Netserver LH 3000 Rack Cabling Guide - Page 51

Rack Storage/12FC is D5991A

Page 51 highlights

Chapter 3 Procedure for Connecting and Routing Cables to the LH 3000r Table 3-3. 230/240 VAC PDU Power and Current Component1 200/240 VAC PDU HP NetServer LH 3000r Model E7671A or E7672A D8230A, 533 MHz, 512 MB D8238A, 600 MHz, 256 MB D8246B, 667 MHz, 256 MB Power (VA) N/A 514 Power (W) N/A Current (A)2 max 16 504 2.3 HP NetServer Rack Storage/12 is D5989A 518 507 2.3 Mass Storage Rack Storage/12FC is D5991A Unit HP Console Switch J1497B 42 29 0.2 Note 1 More ratings are listed in Table 2-9. For a full list of power ratings, see the rack configuration utilities (for instance, Rack Assistant) on the HP Web Site. Note 2 Indicated current ratings are for use in selecting PDU and UPS components and may not reflect actual measured amounts. Description of the Recommended 230/240 VAC Configuration Figure 3-7 shows a UPS connected to the power mains through an attached power cord (appropriate cords are supplied for each country). The UPS has eight IEC 320 receptacles for use with the rack jumper cords. The E7671A PDU connects to the UPS via a detachable line cord, which connects to the PDU via a C-19 plug. This cord connects to the UPS with a C-20 plug. The 200/240 VAC PDU has two IEC 320, C-19 and six IEC 320, C-13 receptacles for connecting rack jumper cords. 47

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67

Chapter 3
Procedure for Connecting and Routing Cables to the LH 3000r
47
Table 3-3. 230/240 VAC PDU Power and Current
Component
1
Model
Power
(VA)
Power
(W)
Current
(A)
2
200/240 VAC
PDU
E7671A or E7672A
N/A
N/A
max 16
HP NetServer
LH 3000r
D8230A, 533 MHz, 512 MB
D8238A, 600 MHz, 256 MB
D8246B, 667 MHz, 256 MB
514
504
2.3
HP NetServer
Mass Storage
Unit
Rack Storage/12 is D5989A
Rack Storage/12FC is D5991A
518
507
2.3
HP Console
Switch
J1497B
42
29
0.2
Note 1
More ratings are listed in Table 2-9. For a full list of power ratings, see the rack
configuration utilities (for instance, Rack Assistant) on the HP Web Site.
Note 2
Indicated current ratings are for use in selecting PDU and UPS components and
may not reflect actual measured amounts.
Description of the Recommended 230/240 VAC Configuration
Figure
3-7
shows a UPS connected to the power mains through an attached power
cord (appropriate cords are supplied for each country). The UPS has eight IEC
320 receptacles for use with the rack jumper cords. The E7671A
PDU connects to
the UPS via a detachable line cord, which connects to the PDU via a C-19 plug.
This cord connects to the UPS with a C-20 plug. The 200/240 VAC
PDU has two
IEC 320, C-19 and six IEC 320, C-13 receptacles for connecting rack jumper
cords.