HP LH4r HP Netserver LH 3000 Rack Cabling Guide - Page 62
Table B -1. Components for Use with the Redundant Switch and the LH 3000r, Note 1, Note 2
View all HP LH4r manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 62 highlights
Appendix B Considerations in Mounting the Redundant Switch Table B -1. Components for Use with the Redundant Switch and the LH 3000r Item APC Redundant Switch Model No. Power Cord from Power Mains to Switch APC UPS Model No. Power or Jumper Cord from Switch to UPS Power or Jumper Cord from Switch to PDU Circuit Limitation North America: 100/120 VAC Mains Application with UPS Application with No UPS SU 042-2 SU 042-1 2 Captive Power Cords with NEMA L5-30P 2 Captive Power Cords with NEMA L5-30P NS2200RM3u Not Used 1 Captive Power Cord with L5-30R Receptacle Not Used Not Used 2 each, E7802A, 4m, 5-20P to C19 3000 VA 3000 VA North America: 208/240 VAC Mains Application with UPS SU 045-1 Application with No UPS SU 045-1 2 Captive Power Cords with L6-20P Plugs 2 Captive Power Cords with L6-20P Plugs NS3000RMT3U Not Used 1 Captive Power Cord with L6-20P Plug Not Used Not Used E7803A, 4.5 m, L6-20P to C19 3000 VA 3000 VA International1: 230/240V Mains Application with UPS Application with No UPS SU 044-1 SU 044-1 2 Detachable Power Cords, Country Specific NS3000RMI3U or NS2200RMI3U2 E7804A, 4m, C20 to C19 2 Detachable Power Cords, Country Specific Not Used Not Used Not Used E7804A, 4m, C20 to C19 3000 VA 3000 VA Note 1. In North America, if 240 VAC is used, refer to these columns. Note 2. This UPS limits circuit to 9.5 Amperes at 2200 VA. 58