DELUXE PROGRAMMABLE THERMOSTAT TROUBLESHOOTING GUIDE Symptom Action Display will not come on. • Check if the thermostat is mounted and latched on the wallplate-mount and latch the thermostat on the wallplate. • Check if the circuit breaker is tripped-reset the circuit breaker. • Check if the fuse is blown-replace the fuse. • Check if the system switch at the equipment is in the Off position-set to On position. • Check wiring between thermostat and HVAC equipment- replace any broken wires. • If 24 Vac is present, proceed with troubleshooting. Temperature settings will not change (Example: cannot set the heating higher or the cooling lower). • Check that the temperature setpoints are: - heating: 40 to 90°F (7 to 31°C) - cooling: 45 to 99°F (9 to 37°C). "Filter" flashing in display. • Indicates a filter timer needs to be reset. - See Viewing and Resetting Timer Settings instructions. Heating will not come • Check that setpoint is above room temperature. on. • Check if the circuit breaker is tripped-reset the circuit breaker. • Check if the fuse is blown-replace the fuse. • Check if the system switch at the equipment is in the Off position-set to On position. • If 24 Vac is present, proceed with troubleshooting. • Wait five minutes for the system to respond. • Set system selection to Heat. Cooling will not come on. • Check that setpoint is below room temperature. • Check if the circuit breaker is tripped-reset the circuit breaker. • Check if the fuse is blown-replace the fuse. • Check if the system switch at the equipment is in the Off position-set to On position. • If 24 Vac is present, proceed with troubleshooting. • Wait five minutes for the system to respond. • Set system selection to Cool. System on indicator Wait a minute after seeing the flame or snowflake and then (flame=heat, check the registers. snowflake=cool) is lit, but no warm or cool air is coming from the registers. 69-1400-1 18

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

DELUXE PROGRAMMABLE THERMOSTAT
69-1400—1
18
TROUBLESHOOTING GUIDE
Symptom
Action
Display will not come
on.
Check if the thermostat is mounted and latched on the
wallplate—mount and latch the thermostat on the
wallplate.
Check if the circuit breaker is tripped—reset the circuit
breaker.
Check if the fuse is blown—replace the fuse.
Check if the system switch at the equipment is in the Off
position—set to On position.
Check wiring between thermostat and HVAC equipment—
replace any broken wires.
If 24 Vac is present, proceed with troubleshooting.
Temperature settings
will not change
(Example: cannot set
the heating higher or
the cooling lower).
Check that the temperature setpoints are:
-
heating: 40 to 90°F (7 to 31°C)
-
cooling: 45 to 99°F (9 to 37°C).
“Filter” flashing in
display.
Indicates a filter timer needs to be reset.
- See Viewing and Resetting Timer Settings instructions.
Heating will not come
on.
Check that setpoint is above room temperature.
Check if the circuit breaker is tripped—reset the circuit
breaker.
Check if the fuse is blown—replace the fuse.
Check if the system switch at the equipment is in the Off
position—set to On position.
If 24 Vac is present, proceed with troubleshooting.
Wait five minutes for the system to respond.
Set system selection to Heat.
Cooling will not come
on.
Check that setpoint is below room temperature.
Check if the circuit breaker is tripped—reset the circuit
breaker.
Check if the fuse is blown—replace the fuse.
Check if the system switch at the equipment is in the Off
position—set to On position.
If 24 Vac is present, proceed with troubleshooting.
Wait five minutes for the system to respond.
Set system selection to Cool.
System on indicator
(flame=heat,
snowflake=cool) is lit,
but no warm or cool air
is coming from the
registers.
Wait a minute after seeing the flame or snowflake and then
check the registers.