Honeywell TB7100A1000 Installation Instructions - Page 10

Table 4. Installer Setup Menu. Continued, Installer, Setup, Number, Installer Setup, Default, - manual

Page 10 highlights

TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT Table 4. Installer Setup Menu. (Continued) Installer Setup Number Installer Setup Name Default Setting All Settings Notes 0300 Changeover 1 0-Manual 1-Auto Only shown if system has both heat and cool stages (ISU 0170). Shown for CNV, HP, PTAC and 4 pipe fan coil (ISU 0170). Not shown for 2 pipe fan coil modes. 0310 Deadband 3°F (2°C) 2 (1.5)-2°F (1.5°C) 3 (2.0)-3°F (2.0°C) 4 (2.5)-4°F (2.5°C) 5 (3.0)-5°F (3.0°C) 6 (3.5)-6°F (3.5°C) 7 (4.0)-7°F (4.0°C) 8 (4.5)-8°F (4.5°C) 9 (5.0)-9°F (5.0°C) Only shown if Automatic Changeover selected (ISU 0300). 0320 Temperature 0 Indication Scale 0-°F 1-°C 0330 Daylight Saving 1 0-Disabled 1-Enabled (US) 0340 Remote Temp 0 Sensor/Remote Setback/ Changeover Input 0-None 1-Remote 10K Indoor 2-Remote 20K Indoor 3-Changeover 2 pipe Fan Coil modes only 4-Changeover 2 pipe Fan Coil modes only Only shown on models that offer remote sensing. NO input (default mode is Heat) NO input (default mode is Cool) 0340 Remote Temp 0 (Non- Sensor/Remote program Setback/ mable) Changeover Input 0-None 1-Remote 10K Indoor 2-Remote 20K Indoor 3-Changeover 2 pipe Fan Coil modes only 4-Changeover 2 pipe Fan Coil modes only 5-Remote Setback 6-Remote Setback Only shown on models that offer remote sensing. NO input (default mode is Heat) NO input (default mode is Cool) Hotel card NO, with 1 second software delay going from UnOcc to Occupied; 2 minute delay going from Occupied to UnOcc. Hotel Card NC, with 1 second software delay going from UnOcc to Occupied; 2 minute delay going from Occupied to UnOcc. 0341 Delay for Remote 0 Setback 0-No Delay 2-2 Minute Delay Only shown if Remote Setback (ISU 0340) is enabled. 0342 Override Option 0 (only available in non-programmable mode) 0-No Override 1-Override This option is only available for non-programmable mode (ISU 0160) 0343 Unoccupied Heating Setpoint (only when remote setback enabled) 60°F 50-65°F 10-18°C 0346 Unoccupied 80°F Cooling Setpoint (only when remote setback is enabled) 75-90°F 24-30°C 0347 Fan Ramping 1 0-Disabled (Lo, Med, Hi) To enable the fan ramping algorithm. Only 1-Enabled available for fan coil or PTAC applications. 0348 Fan Mode 0 0-User can choose To select a particular fan mode: Auto is the fan Cycle or Constant 3 ramp mode. If ramping is not selected, fan mode speed: Low->Med-> automatically defaults to Low Med High (Constant High->Auto-> Low only) and ISU 0348 is unavailable. Only available 1-Cycle Only - Auto only for fan coil or PTAC applications. 62-0273-05 10

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16

TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT
62-0273—05
10
0300
Changeover
1
0—Manual
1—Auto
Only shown if system has both heat and cool
stages (ISU 0170). Shown for CNV, HP, PTAC and
4 pipe fan coil (ISU 0170). Not shown for 2 pipe
fan coil modes.
0310
Deadband
3°F
(2°C)
2 (1.5)—2°F (1.5°C)
3 (2.0)—3°F (2.0°C)
4 (2.5)—4°F (2.5°C)
5 (3.0)—5°F (3.0°C)
6 (3.5)—6°F (3.5°C)
7 (4.0)—7°F (4.0°C)
8 (4.5)—8°F (4.5°C)
9 (5.0)—9°F (5.0°C)
Only shown if Automatic Changeover selected
(ISU 0300).
0320
Temperature
Indication Scale
0
0—°F
1—°C
0330
Daylight Saving
1
0—Disabled
1—Enabled (US)
0340
Remote Temp
Sensor/Remote
Setback/
Changeover Input
0
0—None
1—Remote 10K Indoor
2—Remote 20K Indoor
3—Changeover 2 pipe
Fan Coil modes only
4—Changeover 2 pipe
Fan Coil modes only
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
0340
(Non-
program
mable)
Remote Temp
Sensor/Remote
Setback/
Changeover Input
0
0—None
1—Remote 10K Indoor
2—Remote 20K Indoor
3—Changeover 2 pipe
Fan Coil modes only
4—Changeover 2 pipe
Fan Coil modes only
5—Remote Setback
6—Remote Setback
Only shown on models that offer remote sensing.
NO input (default mode is Heat)
NO input (default mode is Cool)
Hotel card NO, with 1 second software delay going
from UnOcc to Occupied; 2 minute delay going
from Occupied to UnOcc.
Hotel Card NC, with 1 second software delay
going from UnOcc to Occupied; 2 minute delay
going from Occupied to UnOcc.
0341
Delay for Remote
Setback
0
0—No Delay
2—2 Minute Delay
Only shown if Remote Setback (ISU 0340) is
enabled.
0342
Override Option
(only available in
non-programmable
mode)
0
0—No Override
1—Override
This option is only available for non-programmable
mode (ISU 0160)
0343
Unoccupied
Heating Setpoint
(only when remote
setback enabled)
60°F
50-65°F
10-18°C
0346
Unoccupied
Cooling Setpoint
(only when remote
setback is enabled)
80°F
75-90°F
24-30°C
0347
Fan Ramping
1
0—Disabled (Lo, Med, Hi)
1—Enabled
To enable the fan ramping algorithm. Only
available for fan coil or PTAC applications.
0348
Fan Mode
0
0—User can choose
Cycle or Constant 3
speed: Low->Med->
High->Auto-> Low
1—Cycle Only - Auto only
To select a particular fan mode: Auto is the fan
ramp mode. If ramping is not selected, fan mode
automatically defaults to Low Med High (Constant
only) and ISU 0348 is unavailable. Only available
for fan coil or PTAC applications.
Table 4. Installer Setup Menu. (Continued)
Installer
Setup
Number
Installer Setup
Name
Default
Setting
All Settings
Notes