Honeywell TB7100A1000 Installation Instructions - Page 14
Troubleshooting Table 6 - instructions
View all Honeywell TB7100A1000 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 14 highlights
TB7100A1000 MULTIPRO™ MULTISPEED AND MULTIPURPOSE THERMOSTAT System Settings Heat-Thermostat controls the heating system. Off-Both heating and cooling systems are off. Fan is turned off. Cool-Thermostat controls the cooling system. Auto-Thermostat automatically changes between heat and cool operation, depending on indoor temperature. Fan Settings Auto -Fan runs only when heating/cooling system is on. On-Fan runs continuously. Table 5 shows default program settings. See Owner's Guide for complete instructions to change the program. Table 5. Energy saving default schedule. Schedule Period Time Setpoints Heat Cool Fan Setting Occ1 Unocc1 Occ2 Unocc2 8:00am 10:00pm 1:00pm 12:00pm (Noon) 70°F (21°C) 55°F (10°C) 70°F (21°C) 55°F (10°C) 75°F (25.5°C) 85°F (24°C) 75°F (25.5°C) 85°F (24°C) On Auto On Auto Minimum-Off Timer (Compressor Protection) The thermostat has an adjustable Minimum-Off Timer that can be set from zero to five minutes (Factory Setting-five minutes). The Minimum-Off Timer can be bypassed through the Installer System Test or it can be bypassed permanently by setting the Minimum-Off Timer to 0 minutes in the Installer Setup. The Minimum-Off Timer is activated after the compressor turns off: - If the thermostat is system powered (common wire), the Minimum-Off Timer is also activated upon initial startup and after power interruptions. - If there is a call for cooling or heating during the Minimum-Off Time, the thermostat displays "Wait." - When the Minimum Off Timer expires, "Cool On" or "Heat On" (heat pumps only)" appears solidly in the display and the compressor and fan turn on. Indoor Temperature Sensor Allow indoor temperature sensor to absorb the air for a minimum of five minutes before taking a reading. See the Sensor instructions for more information. TROUBLESHOOTING (TABLE 6) Table 6. Troubleshooting. Symptom Possible Cause Display does not come Thermostat is not being powered. on. Action Check for 24 Vac between C and RC. Check that AA batteries are installed correctly and are good. Temperature settings do The upper or lower temperature limits Check temperature setpoints. not change. were reached. Check Installer Setup Numbers 0600 and 0610; modify as needed. The keypad is fully locked. Check Installer Setup Number 0670 to change keypad locked options. Heating or cooling does Thermostat minimum off-time is not come on. activated. System selection not set to Heat or Cool. Wait up to five minutes for the system to respond. Set system Selection to correct position. System type Selection is incorrect. Thermostat is calling for Heating or cooling equipment is not Heat (Heat on) or Cool operating. (Cool on) but no heating or cooling is running. Check Installer Setup Number 0170 and make sure correct System type is chosen. Check wiring. Check Installer Setup Number 0170 and make sure correct system type is chosen. Verify operation of equipment in System Test mode. Heat does not turn on Heating equipment failure. (Heat On is solid in the display). Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the heating equipment to find the cause of the problem. Loose or broken wire connection between thermostat and heating equipment. Check for 24 Vac between the heat terminal (W) and transformer common. If 24 Vac is present, the thermostat is functional. Check the heating equipment to find the cause of the problem. Check for 24 Vac between the heat terminal (W) and transformer common. If voltage is not present, check wire connection (loose or broken) between the thermostat and the heating equipment. 62-0273-05 14