Kenmore 7952 Installation Instructions - Page 6

Kenmore 7952 - Pro 30 in. Dual Fuel Range Manual

Page 6 highlights

Range Placement To eliminate the risk of burns or fire from reaching over heated surface units, cabinet storage space located above the range should be avoided. If cabinet storage space is to be provided, the risk can be reduced by installing a range hood that projects horizontally a minimum of 5" (12.7 cm) beyond the bottom of the cabinet. Gas Supply Installation When shipped from the factory, this unit is designed to operate on 4"(10,16 cm) water column (1.0 kPa) Natural gas manifold pressure. A convertible pressure regulator is connected to the range manifold and MUST be connected in series with the gas supply line. The regulator is located as shown on figure 2 and it is accessible from front of the range. For proper operation, the maximum inlet pressure to the regulator should be no more than 14"(35,56 cm) of water column pressure (3.5 kPa). o Center Line of Range Follow instructions for the type of installation you have Figure 7 if range will be installed with a cabinet on both sides, draw a center line on the floor between the cabinets (see figure 8). If back of range will not be flush with the wall (the location of the outlet may not allow the range to be positioned against the wall), draw a line on the floor where the back edge of the range will be. Now install anti-tip bracket (see "Anti-Tip Bracket Installation", page 10). The inlet pressure to the regulator must be at least 1 " (.25 kPa) greater than the regulator manifold pressure setting. The regulator is set for 4"(10,16 cm) water column (1.0 kPa) Natural gas manifold pressure; the inlet pressure must be at least 5"(12.60 cm) water column (1.25 kPa) Natural gas. For LP/Propane gas, the regulator must be set for 10"(25,4 cm) water column (2.5 kPa) manifold pressure; the inlet pressure must be at least 11 "(27,9 cm) water column (2.75 kPa). The supply line should be equipped with an approved shutoff valve (see Figure 1 I). This valve should be located in the same room as the range and should be in a location that allows ease of opening and closing. Do not block access to the shutoff valve. The valve is for turning on or shutting off gas to the appliance. Open the shutoff valve in the gas supply line. Wait a few minutes for gas to move through the gas line. The gas supply between the shutoff valve and the regulator may be connected by rigid piping or by A.G.A./C.G.A.approved flexible metallic union-connected piping where local codes permit use. The gas supply piping can be through the side wall of the left cabinet. The left side cabinet is an ideal location for the main shutoff valve, if the range is installed within cabinet storage space Connection to Pressure Regulator The regulator is already installed on the appliance. Do not make the connection too tight. The regulator is die cast. Overtightening may crack the regulator resulting in a gas leak and possible fire or explosion. Manual Shutoff Valve GAS FLOW --,1_ Pressure Regulator + i If range will be installed with a cabinet on one side only, move the range into final position. Draw a line on the floor along the side of the range that is not against the cabinet. If back of range will not be flush with the wall (the location of the outlet may not allow the range to be positioned against the wall), draw a line on the floor where the back edge of the range will be. Now install anti-tip bracket (see "Anti-Tip Bracket Installation", page I0). if range will not be installed against a cabinet, move range into final position. Draw a line on the floor along both sides of the range. If back of range will not be flush with the wall (the location of the outlet may not allow the range to be positioned against the wall), draw a line on the floor where the back edge of the range will be. Now install anti-tip bracket (see "Anti-Tip Bracket Installation", page 10). Flare Union Flare Union " ot il N, Nipple Flexible Connector Nipple _ 1 Off Access Cap All connections must be wrench-tightened Figure 8 •t

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24

Range
Placement
To eliminate
the risk of burns or fire from
reaching
over heated
surface units, cabinet
storage
space located
above the range should
be avoided.
If
cabinet
storage
space is to be provided,
the risk can be
reduced
by installing
a range hood that
projects
horizontally
a minimum
of 5" (12.7 cm) beyond the
bottom
of the cabinet.
Gas
Supply
Installation
When shipped from the factory, this unit is designed to
operate on 4"(10,16
cm) water
column (1.0 kPa) Natural
gas manifold
pressure. A convertible pressure regulator is
connected to the range manifold
and MUST be connected
in serieswith
the gas supply line. The regulator is located
as shown on figure 2 and it is accessible from front of the
range.
For
proper
operation,
the maximum
inlet pressure to
the regulator
should be no more than
14"(35,56
cm) of
water
column
pressure (3.5 kPa).
o
Center
Line
of
Range
Follow
instructions
for
the type
of installation
you have
Figure
7
if
range
will
be
installed
with
a cabinet
on
both
sides,
draw
a center
line
on the
floor
between
the
cabinets
(see figure
8). If
back
of
range
will
not
be
flush
with
the
wall
(the
location
of the
outlet
may
not
allow
the
range
to
be positioned
against
the
wall),
draw
a line
on the
floor
where
the
back
edge
of the
range
will
be.
Now
install
anti-tip
bracket
(see
"Anti-Tip
Bracket
Installation",
page
10).
If
range
will
be
installed
with
a cabinet
on
one
side
only,
move the range
into final position.
Draw a line on
the floor
along
the side of the range that
is not against
the cabinet.
If back
of
range
will
not
be flush
with
the
wall
(the location
of the outlet
may not allow the
range to be positioned
against
the wall),
draw a line on
the floor
where the back edge of the range will
be. Now
install
anti-tip
bracket (see "Anti-Tip
Bracket
Installation",
page I0).
The inlet pressure to the regulator
must be at least 1 " (.25
kPa) greater than the regulator manifold
pressure setting.
The regulator
is set for 4"(10,16
cm) water column (1.0
kPa) Natural gas manifold
pressure; the inlet pressure must
be at least 5"(12.60
cm) water
column (1.25 kPa) Natural
gas. For LP/Propane gas, the regulator must be set for
10"(25,4
cm) water column
(2.5 kPa) manifold
pressure;
the inlet pressure must be at least 11"(27,9 cm) water
column (2.75 kPa).
The supply line should be equipped
with an approved
shutoff
valve (see Figure 1I). This valve should be located
in the same room as the range and should be in a location
that allows ease of opening
and closing. Do not block
accessto the shutoff
valve. The valve is for turning
on or
shutting off gas to the appliance. Open the shutoff valve in
the gas supply line. Wait a few
minutes for gas to move
through the gas line.
The gas supply between the shutoff valve and the regulator
may be connected by rigid piping or by A.G.A./C.G.A.-
approved flexible metallic union-connected
piping where
local codes permit
use.
The gas supply piping can be through
the side wall of the
left cabinet. The left side cabinet is an ideal location for the
main shutoff valve, if the range is installed within
cabinet
storage space
Connection
to
Pressure
Regulator
The regulator
is already installed
on the appliance.
if
range
will
not
be
installed
against
a cabinet,
move range into final position.
Draw a line on the floor
along
both sides of the range. If back of
range
will
not
be flush
with
the
wall
(the location
of the outlet
may
not allow the range to be positioned
against the wall),
draw a line on the floor
where the back edge of the
range will be. Now
install anti-tip
bracket
(see "Anti-Tip
Bracket Installation",
page 10).
Do not make the connection
too tight.
The regulator
is die cast. Overtightening
may crack the
regulator
resulting
in a gas leak and possible fire or
explosion.
Manual
GAS FLOW
Pressure
Shutoff
Flare
--,1_
Flare
Regulator
Valve
Union
Union
+
"
i
ot
il
N,
• t
Nipple
Flexible
Nipple _ 1
Off
Connector
Access
Cap
All connections
must be wrench-tightened
Figure
8