[ ELECTRICLaundry Center NOTE: Do not under any circumstances ] remove grounding prong from plug. CIRCUIT- Individual 30 amp. branch circuit fused with 30 amp. time delay fuses or circuit breakers. Use separately fused circuits for washers and dryers, and DO NOToperate a washer and a dryer on the same circuit. \ POWER SUPPLY- 3 wire or 4-wire, 240 volt, single phase, 60 Hz, Alternating Current. Grounding Prong POWER SUPPLY CORD KIT- 3 wire - the dryer MUSTemploy a 3-conductor power supply cord NEMA 10-30 type SRDTrated at 240 volt AC minimum, 30 amp., with 3 open end spade lug connectors with upturned ends or closed loop connectors and marked for use with clothes dryers. See ELECTRICAL CONNECTIONS FOR A 3-WIRE SYSTEM. 4 wire - The dryer MUSTemploy a 4-conductor power supply cord NEMA 14-30 type SRDTor ST (as required) rated at 240 volt AC minimum, 30 amp., with 4 open end spade lug connectors with upturned ends or closed loop connectors and marked for use with clothes dryers. See ELECTRICAL CONNECTIONS FOR A 4-WIRE SYSTEM. (Canada - 4-wire power supply cord is installed on dryer.) Hot and cold water faucets MUSTbe installed within 42 inches (106.68 cm) of your laundry center's water inlet. The faucets MUSTbe 3/4 inch (1.9 cm) garden hose type so inlet hoses can be connected. Water pressure MUST be between 10 and 120 pounds per square inch (maximum unbalance pressure, hot vs. cold, 10 psi). Your water department can advise you of your water pressure. WARNING- Risk of Shock. Appliance grounded to neutral conductor through a link. Grounding through the neutral link is prohibited for (1) New branch circuit installations (2) mobile homes; (3) recreational vehicles; and (4) areaswhere local codes do not permit grounding through the neutral, (1) disconnect the link from the neutral, (2) use grounding terminal or lead to ground appliance in accordance with local codes and (3) connect neutral terminal or lead to branch circuit neutral in usual manner (if the appliance is to be connected by means of a cord kit, use 4-conductor cord for this purpose). USECOPPERCONDUCTOR ONLY. OUTLET RECEPTACLE- NEMA 10-30R receptacle to be located so the power supply cord is accessible when the dryer is in the installed position. (Canada - NEMA 14-30R receptacle.) 1. Drain capable of eliminating 17 gals. per minute. 2. A standpipe diameter of 11/4inches (3.18 cm) minimum. 3. The standpipe height above the floor should be: Minimum height: 33 inches (83.82 cm) Maximum height: 96 inches (244 cm) fm 96"Max. ? 33" Min. (83.82cm) (244cm) NEMA 10-30R NEMA 14-30R [ GASLaundryCenter ] CIRCUIT- Individual 15 amp minimum branch circuit fused with a time delay fuse or circuit breaker. POWER SUPPLY-3 wire, 120 volt single phase, 60 Hz, Alternating Current. NOTE: For installations requiring a longer drain hose, have a qualified technician install a longer hose, PIN 134049201, available from an authorized parts distributor. For drain systems in the floor, install a siphon break kit, available from your local hardware store. POWER SUPPLY CORD -The gas laundry center is equipped with a 120 volt 3-wire power cord. 3

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20

[
ELECTRICLaundry
Center
CIRCUIT- Individual 30 amp. branch circuit fused with 30
amp. time delay fuses or circuit breakers.
Use separately fused circuits for washers and dryers, and
DO
NOToperate
a washer and a dryer on the same circuit.
POWER SUPPLY-
3 wire or 4-wire, 240 volt, single phase, 60
Hz, Alternating
Current.
]
POWER SUPPLY
CORD
KIT- 3 wire
- the dryer
MUSTemploy
a 3-conductor power supply cord NEMA 10-30 type SRDTrated
at 240 volt AC minimum,
30 amp., with 3 open end spade lug
connectors with upturned ends or closed loop connectors and
marked
for
use with
clothes
dryers.
See ELECTRICAL
CONNECTIONS FOR A 3-WIRE SYSTEM.
4 wire
- The dryer
MUSTemploy
a 4-conductor
power supply
cord NEMA 14-30 type SRDTor ST (as required) rated at 240
volt
AC
minimum,
30 amp.,
with
4 open
end spade lug
connectors with upturned ends or closed loop connectors and
marked
for
use with
clothes
dryers.
See ELECTRICAL
CONNECTIONS FOR A 4-WIRE SYSTEM.
(Canada - 4-wire power supply cord is installed on dryer.)
WARNING-
Risk
of
Shock.
Appliance grounded
to neutral
conductor through a link. Grounding through the neutral link is
prohibited
for (1) New branch circuit
installations
(2) mobile
homes; (3) recreational vehicles; and (4) areaswhere local codes
do not permit grounding through the neutral, (1) disconnect the
link from the neutral,
(2) use grounding
terminal
or lead to
ground appliance in accordance with local codes and (3) connect
neutral terminal or lead to branch circuit neutral in usual manner
(if the appliance is to be connected by means of a cord kit, use
4-conductor cord for this purpose). USECOPPERCONDUCTOR
ONLY.
OUTLET RECEPTACLE
- NEMA 10-30R receptacle to be located
so the power supply cord is accessible when the dryer is in the
installed position. (Canada - NEMA 14-30R receptacle.)
NEMA 10-30R
NEMA 14-30R
[
GASLaundryCenter
]
CIRCUIT- Individual 15 amp minimum branch circuit fused with
a time delay fuse or circuit breaker.
POWER
SUPPLY-3
wire, 120 volt single phase, 60 Hz,
Alternating Current.
POWER SUPPLY
CORD -The gas laundry center is equipped
with a 120 volt 3-wire power cord.
NOTE: Do not under
any circumstances
remove grounding
prong from plug.
\
Grounding
Prong
Hot and cold water faucets
MUSTbe
installed within 42 inches
(106.68 cm) of your laundry center's water
inlet. The faucets
MUSTbe
3/4 inch (1.9 cm) garden hose type so inlet hoses can
be connected. Water pressure
MUST
be between
10 and 120
pounds per square inch (maximum unbalance pressure, hot vs.
cold, 10 psi). Your water department
can advise you of your
water pressure.
1. Drain capable of eliminating
17 gals. per minute.
2. A standpipe diameter of 11/4inches (3.18 cm) minimum.
3. The standpipe height above the floor should be:
Minimum
height: 33 inches (83.82 cm)
Maximum height: 96 inches (244 cm)
m
f
96"Max.
?
(244cm)
33" Min.
(83.82cm)
NOTE:
For installations requiring a longer drain hose, have a
qualified
technician
install a longer
hose,
PIN
134049201,
available from an authorized parts distributor. For drain systems
in the floor, install a siphon break kit, available from your local
hardware store.