LiftMaster JDC Installation Manual - English French Spanish - Page 51

Measure DC voltage, Motor DC resistance

Page 51 highlights

Troubleshooting (continued) Code Display Message F04 F04 UNAUTH. STOP (end) F08 F08 NO CONFIG F14 F14 SET LIMITS Description Possible Causes Diagnosis Resolution No motor motion was detected when the operator was attempting to move the motor. Worn motor brushes Motor DC resistance should be less than 3 ohms. If it is greater than 3 ohms, the brushes may fail to maintain contact with the commutator internal to the motor. Replace motor Replace motor brushes (extended duty models only) Powerhead main board motor drive fault Measure DC voltage across motor terminals at main board. In idle state, voltage should be 0. Activate door operator with open/ close. Voltage may vary over a wide range, from several volts up to about 40 volts DC. If voltage is absent during activation, check for other fault codes and correct as necessary. If no other fault codes are present, power cycle the operator and try again. If fault persists, reset settings to factory defaults and reconfigure the operators. If fault still persists, replace main board. Encoder wiring fault Inspect encoder cable for disconnection, bad connection, cut cable, etc. Correct any issues found with encoder wiring Encoder fault or encoder interface fault Go to limit learn process. Number displayed while in door limit learn mode is the encoder position. Jog door several inches in either direction and release button. Number displayed should change. Make sure to cancel changes or set limit again when finished. If encoder position does not change with door movement, the encoder, encoder wiring, and powerhead main board are suspect. Check all three for any visible damage. Attempt power cycling and restoring factory defaults. Replace or repair suspected faulty components. Motor drive fault occurred Check for other fault Review other fault codes codes and perform problem resolution as necessary. Configuration was not found or was reset to factory setting New operator is not configured. If the operator is new, Configure the operator the configuration is per the normal process. initially unset. Operator was factory reset from the menu If the operator is factory reset, the configuration will be unset. Configure the operator per the normal process. End positions are not set or stored Limits were never New product as set out of box shipped does not have any limits set Learn door limits Settings were F14 error reset or invalidated from the menu 51 Re-learn door limits

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86
  • 87
  • 88
  • 89
  • 90
  • 91
  • 92
  • 93
  • 94
  • 95
  • 96
  • 97
  • 98
  • 99
  • 100
  • 101
  • 102
  • 103
  • 104
  • 105
  • 106
  • 107
  • 108
  • 109
  • 110
  • 111
  • 112
  • 113
  • 114
  • 115
  • 116
  • 117
  • 118
  • 119
  • 120
  • 121
  • 122
  • 123
  • 124
  • 125
  • 126
  • 127
  • 128
  • 129
  • 130
  • 131
  • 132
  • 133
  • 134
  • 135
  • 136
  • 137
  • 138
  • 139
  • 140
  • 141
  • 142
  • 143
  • 144
  • 145
  • 146
  • 147
  • 148
  • 149
  • 150
  • 151
  • 152
  • 153
  • 154
  • 155
  • 156
  • 157
  • 158
  • 159
  • 160
  • 161
  • 162
  • 163
  • 164
  • 165
  • 166
  • 167
  • 168
  • 169
  • 170
  • 171
  • 172
  • 173
  • 174
  • 175
  • 176
  • 177
  • 178
  • 179
  • 180
  • 181
  • 182
  • 183
  • 184
  • 185
  • 186
  • 187
  • 188
  • 189
  • 190
  • 191
  • 192
  • 193
  • 194
  • 195
  • 196
  • 197
  • 198
  • 199
  • 200
  • 201
  • 202
  • 203
  • 204
  • 205
  • 206
  • 207
  • 208
  • 209
  • 210
  • 211
  • 212
  • 213
  • 214
  • 215
  • 216

51
Troubleshooting (continued)
Code
Display
Message
Description
Possible Causes
Diagnosis
Resolution
F04
F04
UNAUTH.
STOP
(end)
No motor motion
was detected when
the operator was
attempting to move the
motor.
Worn motor
brushes
Motor DC resistance
should be less than 3
ohms. If it is greater
than 3 ohms, the
brushes may fail to
maintain contact
with the commutator
internal to the motor.
Replace motor
Replace motor brushes
(extended duty models
only)
Powerhead main
board motor drive
fault
Measure DC voltage
across motor
terminals at main
board. In idle state,
voltage should be 0.
Activate door
operator with open/
close.
Voltage may vary
over a wide range,
from several volts up
to about 40 volts DC.
If voltage is absent
during activation, check
for other fault codes and
correct as necessary. If
no other fault codes are
present, power cycle the
operator and try again.
If fault persists, reset
settings to factory
defaults and reconfigure
the operators.
If fault still persists,
replace main board.
Encoder wiring
fault
Inspect encoder
cable for
disconnection, bad
connection, cut
cable, etc.
Correct any issues found
with encoder wiring
Encoder fault or
encoder interface
fault
Go to limit learn
process. Number
displayed while
in door limit learn
mode is the encoder
position.
Jog door several
inches in either
direction and release
button. Number
displayed should
change.
Make sure to cancel
changes or set limit
again when finished.
If encoder position does
not change with door
movement, the encoder,
encoder wiring, and
powerhead main board
are suspect. Check all
three for any visible
damage.
Attempt power cycling
and restoring factory
defaults.
Replace or repair
suspected faulty
components.
Motor drive fault
occurred
Check for other fault
codes
Review other fault codes
and perform problem
resolution as necessary.
F08
F08 NO
CONFIG
Configuration was not
found or was reset to
factory setting
New operator is
not configured.
If the operator is new,
the configuration is
initially unset.
Configure the operator
per the normal process.
Operator was
factory reset from
the menu
If the operator is
factory reset, the
configuration will be
unset.
Configure the operator
per the normal process.
F14
F14 SET
LIMITS
End positions are not
set or stored
Limits were never
set out of box
New product as
shipped does not
have any limits set
Learn door limits
Settings were
reset or invalidated
from the menu
F14 error
Re-learn door limits