LiftMaster SW420 SW420 S3 BOARD Manual - Page 19
Programming
View all LiftMaster SW420 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 19 highlights
Programming Programming 19 01-G0610F13 Figure 13: Main Control Board Switch #1: Operator Programming Refer to Table 5. POLE #1: SINGLE/CLOSE BUTTON ON = Close button only OFF = Open/Close button POLE #2: RIGHT HAND / LEFT HAND ON = Left Hand (hate will open to the left) OFF = Right Hand (gate will open to the right-inside of fence looking out) POLE #3: WARNING DEVICE ON = Warning device will turn on 3 seconds before gate starts to move in either direction. OFF = Warning device disabled. Figure 14 POLE #4: MASTER/SLAVE - SINGLE UNIT ON = Master or Single Unit OFF = Slave Unit RED LED INFORMATION Continuous ON = Unit is on a limit. Blinking 1 flash per second = Normal operation (gate travel or midstop). Blinking 2 flashes per second = Entrapment level 1 (operator reverse to limit). Doc 01-G0610 Rev A