Rheem RAMP-JEZ Installation Instructions - Page 11

Outdoor Unit Below Indoor Coil, Tubing Installation

Page 11 highlights

5. Capillary Tube Coil: DO NOT exceed the Table values for vertical separation for capillary tube coils. 6. Always use the smallest liquid line size permitted to minimize the system charge. 7. Taabbllee 64 mmaayy bbee used for sizing horizontal runs. OUTDOOR UNIT BELOW INDOOR COIL Keep the vertical separation to a minimum. Use the following guidelines when installing the unit: 1. DO NOT exceed the vveerrttiiccaall sseeppaarraattiioonnss aass iinnddiiccaatteeddoonnTTaabbllee 56.. 2. Always use the smallest liquid line size permitted to minimize system charge. 3. No changes are required for either flow check piston coils or expansions coils. 4. Taabbllee 65 mmaayy bbee used for sizing horizontal runs. TUBING INSTALLATION Observe the following when installing correctly sized type "L" refrigerant tubing between the condensing unit and evaporator coil: • If a portion of the liquid line passes through a hot area where liquid refrigerant can be heated to form vapor, insulating the liquid line is required. • Use clean, dehydrated, sealed refrigeration grade tubing. • Always keep tubing sealed until tubing is in place and connections are to be made. • Blow out the liquid and vapor lines with dry nitrogen before connecting to the outdoor unit and indoor coil. Any debris in the line set will end up plugging the expansion device. • As an added precaution, a high quality filter drier is standard on R-410A units. • Do not allow the vapor line and liquid line to be in contact with each other. This causes an undesirable heat transfer resulting in capacity loss and increased power consumption. The vapor line must be insulated. • If tubing has been cut, make sure ends are deburred while holding in a position to prevent chips from falling into tubing. Burrs such as those caused by tubing cutters can affect performance dramatically, particularly on small liquid line sizes. • For best operation, keep tubing run as short as possible with a minimum number of elbows or bends. • Locations where the tubing will be exposed to mechanical damage should be avoided. If it is necessary to use such locations, the copper tubing should be housed to prevent damage. • If tubing is to be run underground, it must be run in a sealed watertight chase. • Use care in routing tubing and do not kink or twist. Use a good tubing bender on the vapor line to prevent kinking. • Route the tubing using temporary hangers, then straighten the tubing and install permanent hangers. Line must be adequately supported. • The vapor line must be insulated to prevent dripping (sweating) and prevent performance losses. Armaflex and Rubatex are satisfactory insulations for this purpose. Use 1/2" minimum insulation thickness, additional insulation may be required for long runs. • Check Taabbllee53ffoorrtthheeccoorrrreeccttvvaappoorrlilnineessizizee..cChheecckkTaTbalbele6sf4oratnhde 5cofrorretchteliqcuoirdlriencet sliiqzuei.d line size. 11

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

11
5.
Capillary Tube Coil:
DO NOT exceed the Table values for vertical separation for capillary tube coils.
6.
Always use the smallest liquid line size permitted to minimize the system
charge.
7.
OUTDOOR UNIT BELOW INDOOR COIL
Keep the vertical separation to a minimum. Use the following guidelines when
installing the unit:
1.
2.
Always use the smallest liquid line size permitted to minimize system charge.
3.
No changes are required for either flow check piston coils or expansions coils.
4.
TUBING INSTALLATION
Observe the following when installing correctly sized type “L” refrigerant tubing
between the condensing unit and evaporator coil:
If a portion of the liquid line passes through a hot area where liquid refrigerant
can be heated to form vapor, insulating the liquid line is required.
Use clean, dehydrated, sealed refrigeration grade tubing.
Always keep tubing sealed until tubing is in place and connections are to be
made.
Blow out the liquid and vapor lines with dry nitrogen before connecting to the
outdoor unit and indoor coil. Any debris in the line set will end up plugging the
expansion device.
As an added precaution, a high quality filter drier is standard on R-410A units.
Do not allow the vapor line and liquid line to be in contact with each other. This
causes an undesirable heat transfer resulting in capacity loss and increased
power consumption. The vapor line must be insulated.
If tubing has been cut, make sure ends are deburred while holding in a position
to prevent chips from falling into tubing. Burrs such as those caused by tubing
cutters can affect performance dramatically, particularly on small liquid line
sizes.
For best operation, keep tubing run as short as possible with a minimum num-
ber of elbows or bends.
Locations where the tubing will be exposed to mechanical damage should be
avoided. If it is necessary to use such locations, the copper tubing should be
housed to prevent damage.
If tubing is to be run underground, it must be run in a sealed watertight chase.
Use care in routing tubing and do not kink or twist. Use a good tubing bender
on the vapor line to prevent kinking.
Route the tubing using temporary hangers, then straighten the tubing and
install permanent hangers. Line must be adequately supported.
The vapor line must be insulated to prevent dripping (sweating) and prevent
performance losses. Armaflex and Rubatex are satisfactory insulations for this
purpose. Use 1/2” minimum insulation thickness, additional insulation may be
required for long runs.
Table 6 may be used for sizing horizontal runs.
DO NOT exceed the vertical separations as indicated on Table 6.
Table 6 may be used for sizing horizontal runs.
Check Table 5 for the correct vapor line size. check Table 6 for the correct liquid
line size.