MECHANICAL CHECKS FLOW CHART Unit Running? High Head Pressure YES Pressure problems? Low Head Pressure Dirty Condenser Coil Low on Charge Inoperative Outdoor Fan Open IPR Valve Overcharge Low Ambient Temperature Recirculation of Condenser Air Inoperative Compressor Valves Non-condensibles Restricted Filter-drier Higher than Ambient Air Entering Condenser Wrong Condenser Fan Rotation Indoor Metering Device Stuck Open Restriction in System Indoor Metering Device Stuck Closed NO Go to Electrical Checks Flow Chart Low Suction Pressure Dirty Filters Dirty Evaporator Inadequate Airflow Broken Indoor Blower Belt Inoperative Indoor Blower Low on Charge Faulty Metering Device Restriction in System Restricted Filter-drier Recirculation of Evaporator Air Wrong Evaporator Blower Rotation Inadequate Ducts 21

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

21
MECHANICAL CHECKS FLOW CHART
Unit Running?
YES
Low Head Pressure
Low Suction Pressure
Open IPR Valve
Dirty Evaporator
Inadequate Airflow
Restricted Filter-drier
NO
Overcharge
Low Ambient Temperature
Inoperative Indoor Blower
Indoor Metering
Device Stuck
Closed
Wrong Condenser Fan Rotation
Pressure problems?
Low on Charge
Dirty Filters
Dirty Condenser Coil
Recirculation of
Condenser Air
Inoperative Compressor
Valves
Low on Charge
Faulty Metering Device
Restriction in System
Restricted Filter-drier
Non-condensibles
Higher than Ambient
Air Entering Condenser
Go to Electrical
Checks Flow Chart
High Head Pressure
Inoperative Outdoor Fan
Broken Indoor
Blower Belt
Restriction in System
Recirculation of
Evaporator Air
Wrong Evaporator
Blower Rotation
Indoor Metering Device
Stuck Open
Inadequate Ducts