Viking RDSCE2305BSS Installation Instructions - Page 6

Electrical Requirements, Electrical shock hazard.

Page 6 highlights

Electrical Requirements Electrical Requirements This product is manufactured with the neutral terminal connected to the cabinet. Use a 3-wire, agency approved, power supply kit with closed loop terminals rated per the National Electrical Code, ANSI/NFPA 70-latest edition (See Rating chart below). If local codes prohibit grounding through the neutral, use a 4-wire, agency approved, power supply kit with closed loop terminals rated per the National Electrical Code, ANSI/NFPA 70-latest edition (See Rating chart below). RATING* Specified Rating of Power Supply Cord Kit and Circuit Protection 120/240 Volts 120/208 Volts Amps 12.5 - 16.5 KW 9.2 - 12.5 KW 40 or 50 16.5 - 17.5 KW 12.5 - 13.5 KW 50 *The National Electric Code calculation for Electrical Load is less than the Total Connected Electrical Load listed on the model/serial rating plate. A GFI shall be used if required by NFPA70 (National Electric Code), federal/state/local laws, or local ordinances. • The required use of a GFI is normally related to the location of a receptacle with respect to any significant sources of water or moisture. Viking Range Corporation will NOT warranty any problems resulting from GFI outlets which are not installed properly or do not meet the requirements below. If the use of a GFI is required, it should be: • Of the receptacle type (breaker type or portable type NOT recommended) • Used with permanent wiring only (temporary or portable wiring NOT recommended) • On a dedicated circuit (no other receptacles, switches or loads in the circuit) • Connected to a standard breaker of appropriate size (GFI breaker of the same size NOT recommended) • Rated for Class A (5 mA +/- 1 mA trip current) as per UL 943 standard • In good condition and free from any loose-fitting gaskets (if applicable in outdoor situations) • Protected from moisture (water, steam, high humidity) as much as reasonably possible WARNING Electrical shock hazard. To avoid the risk of electrical shock, personal injury or death; verify electrical power is turned off at the breaker box until the range is installed and ready to operate, installation by an authorized installer only. Electrical Requirements Electric access area 3-1/2" (8.9 cm) 3" (7.6 cm) SIDE VIEW 6" (15.2 cm) 6" (15.2 cm) 4-3/8" (11.1 cm) REAR VIEW 10 11

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14

11
Electrical Requirements
Electrical Requirements
10
Electrical Requirements
This product is manufactured with the
neutral terminal connected to the cabinet.
Use a 3-wire, agency approved, power
supply kit with closed loop terminals rated
per the National Electrical Code, ANSI/NFPA
70-latest edition (See Rating chart below). If
local codes prohibit grounding through the
neutral, use a 4-wire, agency approved,
power supply kit with closed loop terminals
rated per the National Electrical Code,
ANSI/NFPA 70-latest edition (See Rating
chart below).
RATING* Specified Rating of Power
Supply Cord Kit and Circuit Protection
120/240 Volts
120/208 Volts
Amps
12.5 – 16.5 KW
9.2 – 12.5 KW
40 or 50
16.5 – 17.5 KW
12.5 – 13.5 KW
50
*The National Electric Code calculation for
Electrical Load is less than the Total
Connected Electrical Load listed on the
model/serial rating plate.
A GFI
shall be used if required by NFPA-
70 (National Electric Code),
federal/state/local laws, or local
ordinances.
• The required use of a GFI is normally
related to the location of a receptacle with
respect to any significant sources of water
or moisture.
Electric access area
6”
(15.2 cm)
6”
(15.2 cm)
4-3/8”
4-3/8”
(11.1 cm)
(11.1 cm)
4-3/8”
(11.1 cm)
3-1/2”
(8.9 cm)
3”
(7.6 cm)
REAR VIEW
SIDE VIEW
WARNING
Electrical shock hazard.
To avoid the risk of electrical
shock, personal injury or death;
verify electrical power is turned
off at the breaker box until the range is
installed and ready to operate, installation
by an authorized installer only.
Viking Range Corporation will NOT warranty
any problems resulting from GFI outlets
which are not installed properly or do not
meet the requirements below.
If the use of a GFI is required,
it should be:
• Of the receptacle type (breaker type or
portable type NOT recommended)
• Used with permanent wiring only
(temporary or portable wiring NOT
recommended)
• On a dedicated circuit (no other
receptacles, switches or loads in the circuit)
• Connected to a standard breaker of
appropriate size (GFI breaker of the same
size NOT recommended)
• Rated for Class A (5 mA +/- 1 mA trip
current) as per UL 943 standard
• In good condition and free from any
loose-fitting gaskets (if applicable in
outdoor situations)
• Protected from moisture (water, steam,
high humidity) as much as reasonably
possible