EMC DS-16B Installation Guide

EMC DS-16B - Connectrix Switch - Fibre Channel Manual

EMC DS-16B manual content summary:

  • EMC DS-16B | Installation Guide - Page 1
    It also describes the kits available for mounting them in EMC and non-EMC Racks and includes installation instructions as well. Device 16-port departmental switch Device Model DS-16B2-0D Mounting Kit Model DS16B2-RKH DS16B2-RKL Major sections are • Device Power, Cooling, and Weight Information
  • EMC DS-16B | Installation Guide - Page 2
    Figure 1 DS-16B2 16-Port Switch EMC2041 2 EMC Departmental Switch DS-16B2 Installation Guide
  • EMC DS-16B | Installation Guide - Page 3
    .5 BTU/hr Maximum Weight 12.9 kg (28.5 lbs) Device Dimensions Device DS-16B2 switch DS-16B2 switch with rails Height 4.34 cm 1.0 U 4.44 cm Depth 1.71 in 61.00 cm 24.01 in 1.75 in 61.00 cm 24.01 in Width 42.86 cm 16.87 in 43.18 cm 17.00 in EMC Departmental Switch DS-16B2 Installation Guide 3
  • EMC DS-16B | Installation Guide - Page 4
    clarity. Switch (1 U) Switch (1 U) Filler Panel (2 U) DAE (3.5 U) DAE (3.5 U) DAE (3.5 U) DAE (3.5 U) 39 U DAE (3.5 U) DAE (3.5 U) DAE (3.5 U) DAE (3.5 U) DPE (6.5 U) Figure 2 SPS (1 U) Front Sample Cabinet Installation 4 EMC Departmental Switch DS-16B2 Installation Guide Rear EMC2056
  • EMC DS-16B | Installation Guide - Page 5
    per switch Bezel supports 2 per switch 2 8-foot IEC power cords, straight C13 to C14 straight 2 per switch 2 7.5-foot USA power cords, straight C13 to N5-15P straight (with the (use the ones appropriate for your PDU) DS-16B2-RKL kit only) EMC Departmental Switch DS-16B2 Installation Guide 5
  • EMC DS-16B | Installation Guide - Page 6
    Switch Mounting Kit (DS16B2 - RKH/RKL) Switch Mounting Brackets Front Rails Bezel Short Rear Rails Bezel Supports Figure 3 Rails. Bezel, and Power Cords Long Rear Rails Ac Power Cords EMC2042 6 EMC Departmental Switch DS-16B2 Installation Guide
  • EMC DS-16B | Installation Guide - Page 7
    the securing hardware that is included in the switch mounting kit. The rail assemblies for the EMC CLARiiON® rack come pre-assembled, with the power cord in the rail. Only the long rails, used in third party racks/cabinets, must be assembled. EMC Departmental Switch DS-16B2 Installation Guide 7
  • EMC DS-16B | Installation Guide - Page 8
    -head screw (Qty. 6) Ball stud (Qty. 2) 1 per switch mounting bracket. Used to secure mounting brackets to the rails. 2 per bezel support, to secure the bezel support to the rail assembly. 2 per bezel, to secure the bezel to the rail assembly. 8 EMC Departmental Switch DS-16B2 Installation Guide
  • EMC DS-16B | Installation Guide - Page 9
    (DS16B2 - RKH/RKL) Tools Required for Installation You will need the following tools to complete the installation of the rails and switch(es). Tools Required: #1 Phillips Screwdriver 6-mm (1/4-in.) 8mm (5/16-in.) Nut Driver Nut Driver EMC2065 EMC Departmental Switch DS-16B2 Installation Guide
  • EMC DS-16B | Installation Guide - Page 10
    describes the installation procedures for the DS-16B2 rails. Figure 4 shows a view of the rails installed in a 39 U rack/cabinet. Front Rear Door Removed for Clarity Rear Figure 4 View of the Rails Installed in a 39 U Rack/Cabinet 10 EMC Departmental Switch DS-16B2 Installation Guide EMC2071
  • EMC DS-16B | Installation Guide - Page 11
    is appropriate for your rack/cabinet. To the rear of the cabinet Figure 5 EMC2059 DS-16B2 Short Rear Rails (for the EMC CLARiiON Rack) To the rear of the cabinet Figure 6 EMC2060 DS-16B2 Long Rear Rails (for third Party Racks/Cabinets) EMC Departmental Switch DS-16B2 Installation Guide 11
  • EMC DS-16B | Installation Guide - Page 12
    have three screw holes. See Figures 7 and 7 below. Screw Holes Front Rails Figure 7 Front Flange of the DS-16B2 Rails Short Rear Rails EMC2069 Screw Holes Screw Holes Figure 8 Long Rear Rails Rear Flange of the DS-16B2 Rails EMC2070 12 EMC Departmental Switch DS-16B2 Installation Guide
  • EMC DS-16B | Installation Guide - Page 13
    an illustration of the complete assembly. Keps Nut (2) #10 Flat Washer (2) Short Rear Rail Front Rail Ac Power Cord Figure 9 Ac Power Cord Front Rail DS-16B2 Rails Assembly Short Rear Rail #10 Flat Washer (2) Keps Nut (2) EMC2044 EMC Departmental Switch DS-16B2 Installation Guide 13
  • EMC DS-16B | Installation Guide - Page 14
    Installing the DS-16B2 Rails Assembling the Rails If this is a new installation in an EMC CLARiiON rack, the rails are pre-assembled. Follow these rail assembly instructions only if you are installing the switch in a non-EMC rack/cabinet. 1. Place the front rail down on a table. 2. Lay the ac
  • EMC DS-16B | Installation Guide - Page 15
    Installing the DS-16B2 Rails 3. Insert the slots of the rear adjustable rail onto the threaded posts on the front rail. Be sure that keps nuts. Leave the keps nuts finger tight. See Figure 11. Keps Nut Figure 11 Location of Keps Nuts EMC2066 EMC Departmental Switch DS-16B2 Installation Guide 15
  • EMC DS-16B | Installation Guide - Page 16
    Installing the DS-16B2 Rails 5. Determine where in the rack/cabinet you will locate the switch. 6. Adjust the length of the rail to fit between the channels in the rack/ , the keps nuts can be tightened after the rails have been installed. 16 EMC Departmental Switch DS-16B2 Installation Guide
  • EMC DS-16B | Installation Guide - Page 17
    M5 x 10-mm screws. Hand-tighten the ball stud. NOTE: The ball studs support the bezel. 4. Align the holes in the rear, U-shaped flange of the them after the switch is installed. See Figure 12. 6. Repeat steps 1 through 5 for the other rail. EMC Departmental Switch DS-16B2 Installation Guide 17
  • EMC DS-16B | Installation Guide - Page 18
    the inside of the channel. Rack Rear Rear M5 x 10-mm Pan Head Screw (8) Front Figure 13 Installing Rails in Round-Hole Channels EMC2046 18 EMC Departmental Switch DS-16B2 Installation Guide
  • EMC DS-16B | Installation Guide - Page 19
    the rail to a square-hole channel with 2 square-hole washers and M5 x 16-mm flat head screws (see table on page 8). Leave the screws finger-tight, and tighten them after the switch is installed. 5. Repeat steps 1 through 4 for the other rail. EMC Departmental Switch DS-16B2 Installation Guide 19
  • EMC DS-16B | Installation Guide - Page 20
    front rail flange to the inside of the channel. M5 x 16-mm flat head screw (Qty. 8) Rack Rear Align the rear rail flange to the inside of the channel. Square-Hole Washer (Qty. 8) Figure 14 Installing Rails in Square-Hole Channels EMC2047 20 EMC Departmental Switch DS-16B2 Installation Guide
  • EMC DS-16B | Installation Guide - Page 21
    with three 8-32 x 5/16-in pan-head screws (see table on page 8). Tighten the screws fully. #8-32 x 5/16-in. Pan Head Screw Switch (6) Mounting Bracket Hole Figure 15 Attaching the Switch Mounting Brackets Switch Mounting Bracket EMC2048 EMC Departmental Switch DS-16B2 Installation Guide 21
  • EMC DS-16B | Installation Guide - Page 22
    , as shown in Figure 16. EMC2049 Figure 16 Placing the ac Power Cords on Top of the Switch 4. Push the switch into the rack/cabinet until the hole in the front part of each bracket (the "L"-shaped end) aligns with the hole on the fixed rail. 22 EMC Departmental Switch DS-16B2 Installation Guide
  • EMC DS-16B | Installation Guide - Page 23
    Installing the DS-16B2 Switch 5. Secure the brackets to the rails with two M3 x 8-mm pan head screws (see table on page 8), one on below. 7. Tighten the front screws securing the rails to the front of the rack/cabinet, as shown in Figure 18. EMC Departmental Switch DS-16B2 Installation Guide 23
  • EMC DS-16B | Installation Guide - Page 24
    Tightening the Front and Rear Rail Assembly Screws 8. Install the bezel supports on the flange at the end of the left and right rails. Align the two holes in the bezel support with the top and bottom holes on the flange. See Figure 19. 24 EMC Departmental Switch DS-16B2 Installation Guide
  • EMC DS-16B | Installation Guide - Page 25
    EMC2052 Figure 19 Installing the Bezel Supports 10. Plug the power cords into the outlets at the back of the switch. Slide the excess cable back into the channels in the rails. See Figure 20. Figure 20 Plugging in the ac Power Cords EMC2053 EMC Departmental Switch DS-16B2 Installation Guide 25
  • EMC DS-16B | Installation Guide - Page 26
    the ball stud. Repeat for the other ball stud. See Figure 21. #10 Flat Ball Washer Stud Figure 21 Installing the Ball Studs EMC2054 26 EMC Departmental Switch DS-16B2 Installation Guide
  • EMC DS-16B | Installation Guide - Page 27
    the fibre-optic cables to the switch and run the cables from the switch to the appropriate device. Ensure each fibre- optic cable has a minimum bend radius of 2 inches. 15. Secure the cables with the Velcro strips attached to the rack/cabinet. EMC Departmental Switch DS-16B2 Installation Guide 27
  • EMC DS-16B | Installation Guide - Page 28
    document, even if advised of the possibility of such damages. Trademark Information EMC2, EMC, CLARiiON, and Navisphere are registered trademarks of EMC Corporation. All other trademarks mentioned herein are the property of their respective owners. 28 EMC Departmental Switch DS-16B2 Installation
  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

EMC Departmental Switch DS-16B Installation Guide
1
This document explains the power, cooling, weight, and rack placement
requirements for the 16-port EMC departmental switch shown in Figure
1. It also describes the kits available for mounting them in EMC and
non-EMC Racks and includes installation instructions as well.
Major sections are
Device Power, Cooling, and Weight Information
.................................
3
Device Dimensions
....................................................................................
3
Device Placement Requirements
.............................................................
4
Switch Mounting Kit (DS16B2 - RKH/RKL)
.........................................
5
Installing the DS-16B2 Rails
...................................................................
10
Installing the DS-16B2 Switch
................................................................
21
EMC Departmental Switch
DS-16B2
Installation Guide
P/N 014003075-A01
Device
Device Model
Mounting Kit Model
16-port departmental switch
DS-16B2-0D
DS16B2-RKH
DS16B2-RKL