HP StorageWorks 2/24 FW 07.00.00/HAFM SW 08.06.00 McDATA Products in a SAN Env - Page 290
Heat Dissipation, Clearances
View all HP StorageWorks 2/24 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 290 highlights
Product Specifications Heat Dissipation Clearances Eclipse 1620 SAN Router: Input voltage: 100 to 240 VAC. Input current: 0.35 amps at 208 VAC. Input frequency: 47 to 63 Hz. Eclipse 2640 SAN Router: Input voltage: 100 to 240 VAC. Input current: 0.95 amps at 208 VAC. Input frequency: 47 to 63 Hz. McDATA products have the following maximum heat dissipation characteristics: Intrepid 6064 Director: 490 watts (1,672 BTU/hr). Intrepid 6140 Director: 841 watts (2,873 BTU/hr). Intrepid 10000 Director: 2,496 watts (8,517 BTU/hr). Sphereon 3232 Switch: 245 watts (836 BTU/hr). Sphereon 4300 Switch: 37 watts (127 BTU/hr). Sphereon 4500 Switch: 49 watts (167 BTU/hr). Eclipse 1620 SAN Router: 73 watts (239 BTU/hr). Eclipse 2640 SAN Router: 198 watts (676 BTU/hr). McDATA products have the following cooling airflow clearances. In addition, the Intrepid 10000 Director may require removal from an equipment cabinet (left-side service clearance required) for FRU removal and replacement. Intrepid 6064 Director: Right and left side: 5.1 centimeters (2.0 inches). Front and rear: 7.6 centimeters (3.0 inches). Top and bottom: No clearance required. Intrepid 6140 Director: Right and left side: 2.5 centimeters (1.0 inches). Front and rear: 7.6 centimeters (3.0 inches). Top and bottom: No clearance required. A-4 McDATA Products in a SAN Environment - Planning Manual