Power Requirements, Clearances, Cabinet Footprint, Input voltage, Input current, Input frequency
View all HP StorageWorks 2/24 manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 294 highlights
Product Specifications Power Requirements The Fabricenter cabinet has the following power requirements: Input voltage: 200 to 240 VAC. Input current: 30.0 amps at 208 VAC. Input frequency: 47 to 63 Hz. Clearances The Fabricenter cabinet has the following cooling airflow and service clearances. Cooling airflow clearances: Right and left side: No clearance required. Front and rear: 15.2 centimeters (6.0 inches). Service clearances: Right and left side: No clearance required. Front and rear: 91.4 centimeters (36.0 inches). Cabinet Footprint Figure A-1 illustrates the Fabricenter cabinet footprint. The bottom denotes the front of the cabinet. The illustration includes: 1. Cabinet-leveling screws (eight total). 2. Cooling airflow cutouts (eight total). 3. Fibre Channel cable cutouts (two total). 4. Caster wheel attachments (four total). 5. Power cable cutout (one). A-8 McDATA Products in a SAN Environment - Planning Manual