Function of Outdoor Unit
View all LG LMU240HE manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 47 highlights
Operation Function of Outdoor Unit Outdoor Unit Two Comp algorithm • Inverter Comp is first priority and then Constant Comp is turning on responding to load condtion. Operating Step • Compressor step varies considering condition such as room temp,outdoor temp, operating room number,Temp gap between room temp and set temp and so on. LEV Control • LEV pulse is modulated to keep constant superheat or subcooling. Out door Fan Control • Outdoor fan operates at High or Off to respond to the load condition. R/Valve Control(Heating Model Only) • Convert R/Valve to change cooling to heating, heating to cooling. Defrost Function • After 45 min heating operation, check the defrost condition and if outdoor pipe temp is below 5°C(23°F) and released from deice operation in case outdoor pipe temp is over 12°C(53.6°F) or 9 min cooing mode. • To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to Oil Return System • In single(one) comp operation duration, another comp will operate for 30 seconds every 1 hours. Comp Overload Protection • To protect comp from being overload, protector will turn off the comp. High Pressure Protction • If cycle pressure is too high(around 36.7 kgf/cm2), it will turn off comp A Service Manual 47