LG LMU240HE Service Manual - Page 71
When the louver does not operate., When Vertical Louver does not operate. - problems
View all LG LMU240HE manuals
Add to My Manuals
Save this manual to your list of manuals |
Page 71 highlights
Troubleshooting Guide Trouble 5 When the louver does not operate. When Vertical Louver does not operate. • Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor. • If the regular torque is detected when rotating the Vertical Louver with hands Normal • Check the connecting condition of CN-UP/DOWN Connector • Check the soldering condition(on PWB) of CN-UP/DOWN Connector Check the operating circuit of the Vertical Louver • Confirm that there is DC +12V between pin (RED) of CN-UP/DOWN and GND. • Confirm that there is a soldering short at following terminals. - Between 60 , 61 , 62 and 63 of MICOM - Between 2 , 3 , 4 and 5 of IC01M - Between 12 , 13 , 14 , 15 of IC01M - Between 1 , 2 , 3 , 4 and 5 of CN-UP/DOWN If there are no problems after above checks • Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver Service Manual 71