LG LMU240HE Service Manual - Page 71

When the louver does not operate., When Vertical Louver does not operate. - problems

Page 71 highlights

Troubleshooting Guide Trouble 5 When the louver does not operate. When Vertical Louver does not operate. • Confirm that the Vertical Louver is normally geared with the shaft of Stepping Motor. • If the regular torque is detected when rotating the Vertical Louver with hands Normal • Check the connecting condition of CN-UP/DOWN Connector • Check the soldering condition(on PWB) of CN-UP/DOWN Connector Check the operating circuit of the Vertical Louver • Confirm that there is DC +12V between pin (RED) of CN-UP/DOWN and GND. • Confirm that there is a soldering short at following terminals. - Between 60 , 61 , 62 and 63 of MICOM - Between 2 , 3 , 4 and 5 of IC01M - Between 12 , 13 , 14 , 15 of IC01M - Between 1 , 2 , 3 , 4 and 5 of CN-UP/DOWN If there are no problems after above checks • Confirm the assembly conditions that are catching and interfering parts in the rotation radial of the Vertical Louver Service Manual 71

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86

Service Manual
71
Troubleshooting Guide
When the louver does not operate.
Trouble 5
When Vertical Louver does not operate.
Confirm that the Vertical Louver is normally geared with the shaft of
Stepping Motor.
If the regular torque is detected when rotating the Vertical Louver with
hands
Normal
Check the connecting condition of CN-UP/DOWN Connector
Check the soldering condition(on PWB) of CN-UP/DOWN Connector
Check the operating circuit of the Vertical Louver
Confirm that there is DC
+
12V between pin
(RED) of CN-UP/DOWN and
GND.
Confirm that there is a soldering short at following terminals.
- Between
60
,
61
,
62
and
63
of MICOM
- Between
2
,
3
,
4
and
5
of IC01M
- Between
12
,
13
,
14
,
15
of IC01M
- Between
1
,
2
,
3
,
4
and
5
of CN-UP/DOWN
If there are no problems after above checks
Confirm the assembly conditions that are catching and interfering parts in
the rotation radial of the Vertical Louver