LG LMU240HE Service Manual - Page 74

Multi type Air Conditioner, Troubleshooting Guide

Page 74 highlights

Troubleshooting Guide Error code Title 33 D-Pipe Temp. High Cause of error • Discharge sensor temp. high Check point & Normal condition • Check the discharge pipe sensor. • Check the install condition for over load. • Check the leakage of refrigerent. • Check the SVC V/V open. 115°C(239°F) 100°C(212°F) 95°C(203°F) COMP OFF LEV OPEN(16PULSE/MIN) LEV OPEN(10PULSE/MIN) NORMAL A2UH243FA0/A2UC243FA0 ❑ Check Point 1. Check the install condition for over load. 2. Check the SVC V/V open. 3. Check the leakage of refrigerent. 4. Check the constant compressor. Error code Title 51 Capacitor error Cause of error Check point & Normal condition • Over Capacitor com- • Check the indoor unit capacity. bination • Check the combination table ❑ Check Point 1. Check the indoor unit capacity. 2. Check the combination table. # In the tropical model case ➔ single cycle has no error for over capacity. 74 Multi type Air Conditioner

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62
  • 63
  • 64
  • 65
  • 66
  • 67
  • 68
  • 69
  • 70
  • 71
  • 72
  • 73
  • 74
  • 75
  • 76
  • 77
  • 78
  • 79
  • 80
  • 81
  • 82
  • 83
  • 84
  • 85
  • 86

74
Multi type Air Conditioner
Troubleshooting Guide
Error
Title
Cause of error
Check point & Normal condition
code
33
D-Pipe Temp. High
Discharge sensor
temp. high
Check the discharge pipe sensor.
Check the install condition for over load.
Check the leakage of refrigerent.
Check the SVC V/V open.
Error
Title
Cause of error
Check point & Normal condition
code
51
Capacitor error
Over Capacitor com-
bination
Check the indoor unit capacity.
Check the combination table
Check Point
1. Check the indoor unit capacity.
2. Check the combination table.
In the tropical model case
single cycle has no error for over capacity.
Check Point
1. Check the install condition for over load.
2. Check the SVC V/V open.
3. Check the leakage of refrigerent.
4. Check the constant compressor.
COMP OFF
LEV OPEN(16PULSE/MIN)
LEV OPEN(10PULSE/MIN)
NORMAL
A2UH243FA0/A2UC243FA0
115
°
C(239
°
F)
100
°
C(212
°
F)
95
°
C(203
°
F)