The S60 is shipped with 2 10-32 screws for attaching a ground cable to the, two-hole lug

Page 10 highlights

NOTE: Coat the one-hole lug with an anti-oxidant compound prior to crimping. Bring any un-plated mating surfaces to a shiny finish, and coat with an anti-oxidant prior to mating. Plated mating surfaces must be clean and free from contamination. Step Task 1 Take the 10-32 screw(s) from the package. 2 Cut cable to desired length. Cable length must facilitate the proper operation of fault interrupt circuits. Dell Force10 recommends using of the shortest cable route allowable. 3 Attach the lug to the chassis as shown, using the supplied 10-32 screw(s) with captive internal tooth lock washer. Each screw should be torqued to 20 in-lbs. S55 S60 1 2 4 Attach the other end of the ground cable to a suitable ground point. The rack installation ears are not a suitable grounding point. The S60 is shipped with 2 10-32 screws for attaching a ground cable to the chassis. The cable itself is not included. Dell Force10 recommends a 6AWG two-hole lug, #10 hole size, 63" spacing (not included in shipping) to properly ground the chassis. The two-hole lug must be a UL recognized, crimp-type lug. 8 Installing the Hardware

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28

8
Installing the Hardware
NOTE:
Coat the one-hole lug with an anti-oxidant compound prior to crimping.
Bring any un-plated mating surfaces to a shiny finish, and coat with an anti-oxidant
prior to mating. Plated mating surfaces must be clean and free from contamination.
The S60 is shipped with 2 10-32 screws for attaching a ground cable to the
chassis. The cable itself is not included. Dell Force10 recommends a 6AWG
two-hole lug, #10 hole size, 63" spacing (not included in shipping) to properly
ground the chassis. The two-hole lug must be a UL recognized, crimp-type lug.
Step
Task
1
Take the 10-32 screw(s) from the package.
2
Cut cable to desired length. Cable length must facilitate the proper
operation of fault interrupt circuits. Dell Force10 recommends using of
the shortest cable route allowable.
3
Attach the lug to the chassis as shown, using the supplied 10-32
screw(s) with captive internal tooth lock washer. Each screw should be
torqued to 20 in-lbs.
S55
S60
4
Attach the other end of the ground cable to a suitable ground point. The
rack installation ears are not a suitable grounding point.
1
2