A Workgroup System Tower High-Line Power Examples Warning! Be sure that all circuit breakers are locked in the off position before connecting any power components. Caution: HP recommends that no more than two power supplies be plugged into a single power strip. Important: The configurations shown in this appendix are examples only and do not show all possible combinations of PDUs, UPS, and power cords. C20-C13 power cords are not supplied by HP. If you intend to use the configuration examples with C20-C13 power cords, HP recommends that you check on the availability of the C20-C13 power cords with an HPC-certified reseller when you order the Workgroup System Tower. This appendix provides six different power examples for the Workgroup System Tower, as follows: • Example Configuration 1 (4kVA, N+N redundant enclosure with two 32A International PDUs) • Example Configuration 2 (2.7kVA, N+N redundant enclosure with two 16A PDUs) • Example Configuration 3 (3kVA, N+1 redundant enclosure with a 16A PDU) • Example Configuration 4 (5kVA - 7kVA, N+1 redundant enclosure with a 32A International PDU) • Example Configuration 5 (5kVA, N+N redundant enclosure with a 16A 3-Phase PDU) • Example Configuration 6 (5kVA, N+1 redundant enclosure with a 16A 3-Phase PDU) Figure A-1 provides an example of a 4kVA, N+N redundant enclosure with a 32A International PDU (252663-B31 IEC 309-32A). The extension bars are used to allow other devices to be plugged in. 31

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44

A Workgroup System Tower High-Line Power Examples
Warning!
Be sure that all circuit breakers are locked in the off position before connecting any power
components.
Caution:
HP recommends that no more than two power supplies be plugged into a single power strip.
Important:
The configurations shown in this appendix are examples only and do not show all possible
combinations of PDUs, UPS, and power cords. C20-C13 power cords are not supplied by HP. If
you intend to use the configuration examples with C20-C13 power cords, HP recommends that
you check on the availability of the C20-C13 power cords with an HPC-certified reseller when
you order the Workgroup System Tower.
This appendix provides six different power examples for the Workgroup System Tower, as
follows:
Example Configuration 1 (4kVA, N+N redundant enclosure with two 32A International
PDUs)
Example Configuration 2 (2.7kVA, N+N redundant enclosure with two 16A PDUs)
Example Configuration 3 (3kVA, N+1 redundant enclosure with a 16A PDU)
Example Configuration 4 (5kVA - 7kVA, N+1 redundant enclosure with a 32A International
PDU)
Example Configuration 5 (5kVA, N+N redundant enclosure with a 16A 3-Phase PDU)
Example Configuration 6 (5kVA, N+1 redundant enclosure with a 16A 3-Phase PDU)
Figure A-1
provides an example of a 4kVA, N+N redundant enclosure with a 32A International
PDU (252663-B31 IEC 309-32A). The extension bars are used to allow other devices to be plugged