HP R1500 HP UPS R5000 User Guide - Page 51

Power protection specifications, Voltage specifications, Output tolerance specifications

Page 51 highlights

UPS model Load segment 2 Circuit breaker 20 A¹ Output receptacles Maximum current 2 x IEC-320-C19 2 x IEC-320-C13 16 A per receptacle² 10 A per receptacle R5000 INTL 1 2 20 A¹ 20 A¹ 2 x IEC-320-C19 2 x IEC-320-C13 1 x IEC-309-32A 2 x IEC-320-C19 2 x IEC-320-C13 16 A per receptacle² 10 A per receptacle Up to full UPS power rating 16 A per receptacle² 10 A per receptacle 1 The circuit breakers protect the C19 and C13 outlets. 2 If an extension bar is connected to a C19 receptacle, the maximum current for each C13 receptacle on the extension bar is 10 A. The total maximum current for the extension bar is 12 A. Power protection specifications UPS model R5000 NA/JPN R5000 INTL VA 5000 5000 Nominal power rating (W) 4500 4500 Nominal voltage setting 200/208, 220, 230, 240 200/208, 220, 230, 240 Voltage specifications Configuration setting (VAC) 200/208 220 230 240 Available nominal output voltage (VAC) 204 220 230 240 Output tolerance specifications Source of power Utility power (nominal range) Battery power Regulation -10% to +6% of nominal output voltage rating (within the guidelines of the Computer Business Equipment Manufacturers Association) ±5% of nominal output voltage rating Output feature specifications Feature Online efficiency Voltage wave shape Specification 94% nominal input voltage Sine wave; 5% THD with typical PFC load Specifications 51

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19
  • 20
  • 21
  • 22
  • 23
  • 24
  • 25
  • 26
  • 27
  • 28
  • 29
  • 30
  • 31
  • 32
  • 33
  • 34
  • 35
  • 36
  • 37
  • 38
  • 39
  • 40
  • 41
  • 42
  • 43
  • 44
  • 45
  • 46
  • 47
  • 48
  • 49
  • 50
  • 51
  • 52
  • 53
  • 54
  • 55
  • 56
  • 57
  • 58
  • 59
  • 60
  • 61
  • 62

Specifications 51
UPS model
Load
segment
Circuit
breaker
Output receptacles Maximum current
2
20 A¹
2 x IEC-320-C19
16 A per receptacle²
2 x IEC-320-C13
10 A per receptacle
R5000 INTL
1
20 A¹
2 x IEC-320-C19
16 A per receptacle²
2 x IEC-320-C13
10 A per receptacle
1 x IEC-309-32A
Up to full UPS power rating
2
20 A¹
2 x IEC-320-C19
16 A per receptacle²
2 x IEC-320-C13
10 A per receptacle
1
The circuit breakers protect the C19 and C13 outlets.
2
If an extension bar is connected to a C19 receptacle, the maximum current for each C13 receptacle on the extension
bar is 10 A. The total maximum current for the extension bar is 12 A.
Power protection specifications
UPS model
VA
Nominal power
rating (W)
Nominal voltage
setting
R5000 NA/JPN
5000
4500
200/208, 220,
230, 240
R5000 INTL
5000
4500
200/208, 220,
230, 240
Voltage specifications
Configuration setting (VAC)
Available nominal output voltage
(VAC)
200/208
204
220
220
230
230
240
240
Output tolerance specifications
Source of power
Regulation
Utility power (nominal
range)
-10% to +6% of nominal output voltage rating
(within the guidelines of the Computer Business
Equipment Manufacturers Association)
Battery power
±5% of nominal output voltage rating
Output feature specifications
Feature
Specification
Online efficiency
94% nominal input voltage
Voltage wave shape
Sine wave; 5% THD with typical PFC load