Honeywell NSLAN1 Installation Guide - Page 15

NSLAN1 Connection

Page 15 highlights

NSLAN1 Ethernet Board Installation Guide NSLAN1 Connection NSLAN1 Connection 1 NS2 per. NSLAN1 64 IP Connections Per System 100BaseT (CAT 5) 100 Ft. Max. HUB NStar Server NS2 Panel Earth Ground Dipswitch Settings S1-S5: Panel Address S6: OFF (RS-485 Disable) S7: ON (57,600 Baud Rate) S8-S10: OFF { A-1 } NS2 Panel Earth Ground 100BaseT (CAT 5) 100 Ft. Max. { A-1 } NS2 Enclosure is recommended to be grounded individually to earth ground. 100BaseT (CAT 5) 100 Ft. Max. Dipswitch Settings S1-S5: Panel Address S6: OFF (RS-485 Disable) S7: ON (57,600 Baud Rate) S8-S10: OFF Document TD1164, Revision A © 2005 Honeywell International 13 NSLAN1 Ethernet Board Installation Guide

  • 1
  • 2
  • 3
  • 4
  • 5
  • 6
  • 7
  • 8
  • 9
  • 10
  • 11
  • 12
  • 13
  • 14
  • 15
  • 16
  • 17
  • 18
  • 19

NSLAN1 Ethernet Board Installation Guide
NSLAN1 Connection
Document TD1164, Revision A
NSLAN1 Ethernet Board
© 2005 Honeywell International
13
Installation Guide
NSLAN1 Connection
1 NS2 per. NSLAN1 64 IP Connections Per System
NStar Server
HUB
100BaseT (CAT 5) 100 Ft. Max.
100BaseT (CAT 5) 100 Ft. Max.
NS2
Panel
100BaseT (CAT 5) 100 Ft. Max.
NS2
Panel
Dipswitch Settings
S1-S5: Panel Address
S6: OFF (RS-485 Disable)
S7: ON (57,600 Baud Rate)
S8-S10: OFF
Dipswitch Settings
S1-S5: Panel Address
S6: OFF (RS-485 Disable)
S7: ON (57,600 Baud Rate)
S8-S10: OFF
Earth
Ground
Earth
Ground
{ A-1 }
{ A-1 }
NS2 Enclosure
is recommended to be grounded
individually to earth ground.