12 Technical Specifications Model SMART700RT1U SMART750RT1U SMART1000RT1U SMC1000RT1U SMART1500RT1U SMC1500RT1U Nominal Voltage and Input Range 100V~, 120V~, 127V~, 80V-162V (High Sensitivity) 70V-162V (Low Sensitivity) Nominal Input Frequency and Tolerance 50 Hz (-4/+20 Hz for High Sensitivity; -10/+20 Hz for Low Sensitivity) 60 Hz (-4/+10 Hz) Nominal Output Voltage 120V~ in Line Mode and 120V~ in Battery Mode Nominal Output Frequency 50 Hz (-4/+20 Hz for High Sensitivity; -10/+20 Hz for Low Sensitivity) 60 Hz (-4/+10 Hz) Output Voltage Regulation in Line Mode 120V~ (-16%/+16%) Output voltage regulation in Battery Mode: 120V~ (-10%/+6%) Nominal output power in W / VA: 420W/700VA @ 120V~/127V~ 350W/583VA 100V~ 600W/750VA @ 120V~/127V~ 500W/625VA @ 100V~ 770W/1000VA @ 120V ~/127V~ 641W/833VA @ 100V~ 600W/1000VA @ 120V ~ /127V~ 500W/833VA @ 100V~ 1100W/1440VA @ 120V ~/127V~ 825W/1080VA (100V~) 1100W/1440VA @ 120V ~/127V~ 825W/1083VA (100V~) Output Voltage Waveform Sinusoidal in Line Mode and in Battery Mode Maximum Output Current @ P.F. 5.83A @ 100V~ 5.84A @ 120V~ 5.52A @ 127V~ 6.25A @ 100V~ 6.25A @120V~ 5.91A @127V~ 8.33A @ 100V~ 8.34A @120V~ 7.88A @ 127V~ 8.33A @ 100V~ 8.34A @120V~ 7.88A @ 127V~ 10.8A @ 100V~ 12A @ 120V~ 11.34A @ 127V~ 10.8A @ 100V~ 12A @ 120V~ 11.34A @ 127V~ P.F. = 0.6 P.F. = 0.8 P.F. = 0.8 P.F. = 0.6 P.F. = .76 P.F. = .76 Efficiency with Nominal Load 98% Maximum Operating Altitude at 100% of Nominal Power 3280 ft. (1000 m) Online Overload Capability